135
Installation Manual
Appendix / Technical Specifications (DC)
Product Model
PP2-DC-
10/15/20-9600
PP2-DC-
10/15/20-8600
PP2-DC-
10/15/20-7600
PP2-DC-
10/15/20-7000
PP2-DC-
10/15/20-6000
PP2-DC-
10/15/20-5000
Voltage, Nominal
102.4 VDC (89.6 – 115.2 VDC)/ 153.6 VDC (134.4 – 172.8 VDC/ 204.8 VDC (179.2 – 230.4 VDC)
Continuous Charge Current
50 ADC
Continuous Discharge
Current
50 ADC
Maximum Charge Current
60 ADC
Maximum Discharge
Current
60 ADC
Continuous Charge Power
(Nominal)
5120/7700/9600 W
5120/7700/8600 W
5120/7600/7600 W
5120/7000/7000 W
5120/6000/6000 W
5000/5000/5000 W
Continuous Discharge
Power (Nominal)
5120/7700/9600 W
5120/7700/8600 W
5120/7600/7600 W
5120/7000/7000 W
5120/6000/6000 W
5000/5000/5000 W
Maximum Charge Power
(Nominal)
6150/7700/10,240
W
6150/7700/10,240
W
6150/7700/9120 W
6150/7700/8400 W
6150/7200/7200 W
6000/6000/6000 W
Maximum Discharge
Power (Nominal)
6150/7700/10,240
W
6150/7700/10,240
W
6150/7700/9120 W
6150/7700/8400 W
6150/7200/7200 W
6000/6000/6000 W
Optimum Operating
Temperature Range
0° C to 30° C (32° F to 86° F)
See detailed temperature guidelines below.
Do not install outdoors in climates where the temperature drops below 0
°
C (32
°
F) for extended periods.
Do not install in direct sunlight.
Charge Temperature
(0 °C to 55 °C)
Discharge Temperature
(-20 °C to 55 °C)
Communication Interface
RJ-45 RS-485
Power Switch, ON / OFF
Yes
Cycles
For Daily Cycle Applications
Service Life (40% Capacity
Reduction)
10 Years
Altitude
2000 m
Dimensions (W / H / D)
(BMS & battery module)
17.5” x 7.5” x 8.9” / 445mm x 190mm x 226mm
Dimensions (W / H / D) 10
kWh assembled battery
enclosure
27.5” x 50” x 9” / 700mm x 1270mm x 230mm
Dimensions (W / H / D) 5
kWh assembled battery
enclosure
27.5” x 50” x 9” / 700mm x 1270mm x 230mm
Weight BMS
33 lb. / 15 kg
Weight (battery only, 1
module)
62 lb. / 28 kg
Weight (Total batteries)
400 lb. (180 kg) / 535 lb. (240 kg) / 705 lb. (320 kg)
Warranty Battery
10 years
SOC
Charge/Discharge Rate
>80%
Charge rate will gradually slow down until SOC reaches 100%
0% to 100%
Charge rate is derated when temperature is below 10° C (i.e. 50° F)
0% to 100%
Charging will stop when cell temperature goes below or at 0° C (32° F)
0% to 100%
Discharging will stop when cell temperature goes below -20° C (-4° F).