69
Installation Manual
Partial-Home Backup Wiring Connection Process
CAUTION:
To reduce the risk of fire, do not connect to an
AC load center (circuit breaker panel) having multi wire
branch circuits connected.
Pour réduire le risque d’incendie, ne vous connectez pas
à un centre de chargement AC (panneau de disjoncteur)
ayant des circuits de branche multi-fil connectés.
Do not use aluminum cables.
Inverter / Partial-Home
Model Number
Load "Breaker" Specification (A)
PP2-AC or DC-5000-10/15/20
30A
PP2-AC or DC-6000-10/15/20
30A
PP2-AC or DC-7000-10/15/20
35A
PP2-AC or DC-7600-10/15/20
40A
PP2-AC or DC-8600-10/15/20
40A
PP2-AC or DC-9600-10/15/20
50A
Model Number
Grid "Wire Size" Rated for (A)
PP2-AC or DC-5000-10/15/20
35A
PP2-AC or DC-6000-10/15/20
40A
PP2-AC or DC-7000-10/15/20
45A
PP2-AC or DC-7600-10/15/20
50A
PP2-AC or DC-8600-10/15/20
50A
PP2-AC or DC-9600-10/15/20
50A