Understanding the % of Load Bar
The 10-segment LED bar graph at the bottom left of the IQ 250/260 front panel provides a graphic representation of
Amps. The segments light according to the load, as shown in the % Load Segment Table below.
When the Load is over 120% of Full Load, all segments flash “On” (1.5 secs) and “Off” (0.5 secs).
% of Load Segment Table
Segments
Load >= % Full Load
none
no load
1
1%
1-2
15%
1-3
30%
1-4
45%
1-5
60%
1-6
72%
1-7
84%
1-8
96%
1-9
108%
1-10
120%
All Blink
>120%