![background image](http://html1.mh-extra.com/html/eaton/iq-250/iq-250_user-and-installation-manual_3836163040.webp)
5-2
IB02601006E
www.eaton.com
Chapter 5:
Communication Installation IQ 250/260 Meter
Figure 5.2 shows the detail of a 2-wire RS485 connection.
Figure 5.2: 2-wire RS485 Connection
NOTES:
For All RS485 Connections:
• Use a shielded twisted pair cable 22 AWG (0.33 mm2) or thicker, and ground the shield, preferably at one location
only.
• Establish point-to-point configurations for each device on a RS485 bus: connect (+) terminals to (+) terminals;
connect (-) terminals to (-) terminals.
• You may connect up to 31 meters on a single bus using RS485. Before assembling the bus, each meter must have
a unique address: refer to Chapter 8 for instructions.
• Protect cables from sources of electrical noise.
• Avoid both “Star” and “Tee” connections (see Figure 5.4).
•
No more than two cables
should be connected
at any one point
on an RS485 network, whether the connections
are for devices, converters, or terminal strips.
• Include all segments when calculating the total cable length of a network. If you are
not
using an RS485 repeater,
the maximum length for cable connecting all devices is 4000 feet (1219.20 meters).
• Connect shield to RS485 Master and individual devices as shown in Figure 5.3. You may also connect the shield
to earth-ground at one point.
• Termination Resistors
(
RT
) may be needed on both ends for longer length transmission lines. However, since
the meter has some level of termination internally, Termination Resistors may not be needed. When they are used,
the value of the Termination Resistors is determined by the electrical parameters of the cable.
Figure 5.3 shows a representation of an RS485 Daisy Chain connection.
Figure 5.3: RS485 Daisy Chain Connection
Summary of Contents for IQ 250
Page 2: ......
Page 22: ...3 6 IB02601006E www eaton com Chapter 3 Mechanical Installation IQ 250 260 Meter...
Page 38: ...4 16 IB2601006E www eaton com Chapter 4 Electrical Installation IQ 250 260 Meter...
Page 104: ...A 6 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter...
Page 134: ...A IQ 250 260 Meter Appendix B Modbus Mapping www eaton com IB02601006E MM 28...