Chapter 2:
Overview and Specifications IQ 250/260 Meter
Voltage and Current Inputs
Universal Voltage Inputs
Voltage Inputs allow measurement up to 576VAC (Phase to Reference) and 721VAC (Phase to
Phase). This insures proper meter safety when wiring directly to high voltage systems. One unit will
perform to specification on 69 Volt, 120 Volt, 230 Volt, 277 Volt, and 347 Volt power systems.
NOTE:
Higher voltages require the use of potential transformers (PTs).
Current Inputs
The unit supports a 5 amp or a 1 amp secondary for current measurements.
NOTE:
The
s
econdary current must be specified and ordered with the meter.
The IQ 250/260 Current Inputs use a unique dual input method:
Method 1: CT Pass Through
The CT passes directly through the meter without any physical termination on the meter. This
insures that the meter cannot be a point of failure on the CT circuit. This is preferable for utility
users when sharing relay class CTs. No Burden is added to the secondary CT circuit.
Method 2: Current “Gills”
This unit additionally provides ultra-rugged Termination Pass Through Bars that allow CT leads to be
terminated on the meter. This, too, eliminates any possible point of failure at the meter. This is a
preferred technique for insuring that relay class CT integrity is not compromised (the CT will not
open in a fault condition).
Summary of Contents for IQ 250
Page 2: ......
Page 22: ...3 6 IB02601006E www eaton com Chapter 3 Mechanical Installation IQ 250 260 Meter...
Page 38: ...4 16 IB2601006E www eaton com Chapter 4 Electrical Installation IQ 250 260 Meter...
Page 104: ...A 6 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter...
Page 134: ...A IQ 250 260 Meter Appendix B Modbus Mapping www eaton com IB02601006E MM 28...