Chapter 2:
IQ 250/260 Meter Overview and Specifications
www.eaton.com
IB02601006E
2- 7
Isolation
All Inputs and Outputs are galvanically isolated to 2500 Vac
Environmental Rating
Storage:
(-20 to +70)
0
C
Operating:
(-20 to +70)
0
C
Humidity:
to 95% RH Non-condensing
Faceplate Rating:
NEMA12 (Water Resistant), Mounting Gasket Included
Measurement Methods
Voltage, Current:
True RMS
Power:
Sampling at over 400 Samples per Cycle on All Channels
Update Rate
Watts, VAR and VA:
Every 6 cycles (e.g., 100 ms @ 60 Hz)
All other parameters:
Every 60 cycles (e.g., 1 s @ 60 Hz)
1 second for current only measurement, if reference
voltage is not available
Communication
Standard:
1. RS485 Port through Back Plate
2. Energy Pulse Output through Back Plate
Protocols:
Modbus RTU, Modbus ASCII, DNP 3.0
Com Port Baud Rate:
9,600 to 57,600 bps
Com Port Address:
001-247
Data Format:
8 Bit, No Parity