Appendix C:
IQ 250/260 Meter Using DNP Mapping for IQ 250/260
www.eaton.com
IB02601006E
C-3
DNP Lite Register Map
Object 10 – Binary Output States
Object Point Var Description
Format
Range
Multiplier
Units Comments
10 0 2
Reset Energy
Counters
BYTE
Always 1
N/A
None Read by Class 0 Only
10 1 2
Change
to
Modbus
RTU Protocol
BYTE
Always 1
N/A
None Read by Class 0 Only
10 2 2
Reset Demand
Cntrs (Max / Min )
BYTE
Always 1
N/A
None Read by Class 0 Only
Object 12 – Control Relay Outputs
Object
Point
Var
Description
Format
Range
Multiplier
Units
Comments
12 0 1
Reset
Energy
Counters
N/A
N/A
N/A
none Responds to Function 5
(Direct Operate), Qualifier
Code 17x or 28x, Control
Code 3, Count 0, On 0 msec,
Off 1 msec ONLY.
12 1 1
Change
to
Modbus RTU
Protocol
N/A
N/A
N/A
none Responds to Function 6
(Direct Operate - No Ack),
Qualifier Code 17x, Control
Code 3, Count 0, On 0 msec,
Off 1 msec ONLY.
12 2 1
Reset
Demand
Counters (Max /
Min)
N/A
N/A
N/A
none Responds to Function 5
(Direct Operate), Qualifier
Code 17x or 28x, Control
Code 3, Count 0, On 0 msec,
Off 1 msec ONLY.
Object 20 – Binary Counters (Primary Readings) - Read via Class 0 only
Object
Point
Var
Description
Format
Range
Multiplier
Units
Comments
20 0 5
W-hours,
Positive
UINT32 0
to
99999999
Multiplier = 10(n-d),
where n and d are
derived from the
energy format. n =
0, 3, or 6 per
energy format scale
and d = number of
decimal places.
W hr
example:
energy format = 7.2K and W-
hours counter = 1234567 n=3
(K scale), d=2 ( 2 digits after
decimal point), multiplier =
10(3-2) = 101 = 10, so energy
is 1234567 * 10 Whrs, or
12345.67 KWhrs
20 1 5
W-hours,
Negative
UINT32 0
to
99999999
W
hr
20 2 5
VAR-hours,
Positive
UINT32 0
to
99999999
VAR
hr
20 3 5
VAR-hours,
Negative
UINT32 0
to
99999999
VAR
hr
20 4 5
VA-hours,
Total
UINT32
0 to
99999999
VA
hr
Summary of Contents for IQ 250
Page 2: ......
Page 22: ...3 6 IB02601006E www eaton com Chapter 3 Mechanical Installation IQ 250 260 Meter...
Page 38: ...4 16 IB2601006E www eaton com Chapter 4 Electrical Installation IQ 250 260 Meter...
Page 104: ...A 6 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter...
Page 134: ...A IQ 250 260 Meter Appendix B Modbus Mapping www eaton com IB02601006E MM 28...