8-30
IB02601006E
www.eaton.com
Chapter 8:
Programming the IQ 250/260 IQ 250/260 Meter
Performing Manual Relay Control
1. Click
Tools>Relay Control
. You will see the screen
shown on the right.
This screen allows you to
manually set
the
state
of
any installed
Relay Output/Digital Input
cards.
2. The screen displays the
current
Relay state. To
change the state:
a. Select the state you want in the
Select New State
field.
b.
Click
the
checkbox
next to the
Relays
you want to
change
to the new state.
c. Click
Apply
.
NOTE
: If this feature is
Password Protected
, the
Enter Password
screen opens.
3. Click
OK
to close the screen.
NOTES:
• A Relay
cannot be manually controlled
if a
Limit
has been assigned to it. See the instructions for
configuring a Relay Output/Digital Input Card, earlier in this chapter. (This only applies to the IQ 260 meter.)
• If the
Relay State
field is “
State is Unknown
,” verify that the
Relay configuration
is correct. You may also
see this message after you have performed a
Reset
. Select a
New State
for the Relay and click
Apply
.
Performing Firmware Flash Update
1. Click
Tools>Flash Me
. You will see the screen
shown on the right.
This function allows you to update the IQ 250/260’s
firmware.
2. Click
Browse
to locate the flash file.
3. Click
Flash
to update the firmware with the flash file.
4. When Flash is complete, click
Exit
to close the
screen.
This Bar Shows Flashing Progress
NOTE: If Flash Update fails, you will see a message to that effect.
Check
Device Status
(see instructions
on the previous page) to see if your meter is in
Boot Mode
.
• If the meter is in Boot Mode,
uncheck
the
Starting from Run
Mode
box in the Flash Me screen and try flash
updating the firmware again.
• If the meter’s status is not displayed in the
Device Status
screen, the meter may be stuck in Boot Mode. If
you are certain the communication settings are correct for the meter, try connecting to the meter using the
following defaults:
Address
001
Baud Rate
9600
Protocol
Modbus RTU
Once you connect to the meter, you can try flash upgrading again
.
Flashing progress states and messages are
shown here: shows you current state of flashing
the firmware and any relevant output messages.
Communications messages display here
(messages being sent to the meter).
Summary of Contents for IQ 250
Page 2: ......
Page 22: ...3 6 IB02601006E www eaton com Chapter 3 Mechanical Installation IQ 250 260 Meter...
Page 38: ...4 16 IB2601006E www eaton com Chapter 4 Electrical Installation IQ 250 260 Meter...
Page 104: ...A 6 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter...
Page 134: ...A IQ 250 260 Meter Appendix B Modbus Mapping www eaton com IB02601006E MM 28...