Chapter 8:
Programming the IQ 250/260 IQ 250/260 Meter
Configuring Limits (IQ 260 Only)
Use this screen to assign
Limits
for the meter.
Functional Overview for Limits
:
Limits
are
transition
points
used to divide
acceptable
and
unacceptable
measurements. When a value goes
above or below the limit, an
out-of-limit condition
occurs. You can set and configure up to
eight Limits
for the
IQ 260 meter.
Once they are configured, you can
view
the
out-of-Limits
(or
Alarm
)
conditions
in the
Limits Polling
screen.
You can assign the
eight limits
to readings from
six groups
of parameters:
•
Readings
(Instantaneous Voltage; Instantaneous Current; Total and Per Phase Power and Power Factor;
Frequency; and Neutral Current)
•
Demand
(Current; Per Phase, Total Power and Power Factor)
•
Maximums
(Maximum values for all of the readings listed above, including (for IQ 260) THD voltage and
currents)
•
Minimums
(Minimum values for all of the readings listed above, including (for IQ 260) THD voltage and
currents)
•
Phase Angle
(For voltage and current)
•
THD
(For IQ 260, voltage and current)
From the
Tree Menu
, click
Power Quality and Alarm Settings>Limits
.
The
current settings
for
Limits
are shown in the
screen.
The bottom of the screen shows the
Full Scale
values
for:
• Voltage
• Current
• Frequency
• Power
• Power Total
• Power Factor
• THD
• Phase Angles
1. Select a limit by double-clicking on the
Assigned
Channel
field.
2. You will see the screen on the right. Select a
Group
and an
Item
for the
Limit
.
3. Click
OK
.
Summary of Contents for IQ 250
Page 2: ......
Page 22: ...3 6 IB02601006E www eaton com Chapter 3 Mechanical Installation IQ 250 260 Meter...
Page 38: ...4 16 IB2601006E www eaton com Chapter 4 Electrical Installation IQ 250 260 Meter...
Page 104: ...A 6 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter...
Page 134: ...A IQ 250 260 Meter Appendix B Modbus Mapping www eaton com IB02601006E MM 28...