Chapter 6:
IQ 250/260 Meter Using the IQ 250/260
www.eaton.com
IB02601006E
6-9
Configuring Connection Setting
1. Press the
Enter
button when
Cnct
is in the A window. The
Cnct
screen appears.
2. Press the
Right
button
or
Down
button to select a configuration.
The choices are:
• 3 Element Wye (
3 EL WYE
)
• 2.5 Element Wye (
2.5EL WYE
)
• 2 CT Delta (
2 Ct dEL
)
NOTE: If you are prompted to enter a password, refer to the instructions
earlier in this chapter.
3. When you have made your selection, press the
Menu
button twice.
4. The
STOR ALL YES
screen appears. Press
Enter
to save the setting.
Use buttons to select configuration
Configuring Communication Port Setting
Port configuration consists of :
Address
(a three digit number),
Baud Rate
(9600; 19200; 38400; or 57600), and
Protocol
(DNP 3.0; Modbus RTU; or Modbus ASCII).
1. Press the
Enter
button when
POrt
is in the A window.
The
Adr
(address) screen appears. You can either:
• Enter the address.
• Access one of the other Port screens by pressing the
Enter
button: press
Enter
once to access the
bAUd
screen (Baud Rate); press
Enter
twice to access the
Prot
screen (Protocol).
a.
To enter the Address, from the Adr screen:
•
Use the
Down
button to select the number value for a digit.
• Use the
Right
button to move to the next digit.
b.
To select the Baud Rate, from the bAUd screen:
Use the
Right
button or the
Down
button to select the setting you want.
c.
To select the Protocol, from the Prot screen:
Press the
Right
button or the
Down
button to select the setting you want.
NOTE: If you are prompted to enter a password, refer to the instructions earlier in this chapter.
2. When you have finished making your selections, press the
Menu
button twice.
3. The
STOR ALL YES
screen appears. Press
Enter
to save the settings.
Use buttons to enter Address Use buttons to select Baud Rate Use buttons to select Protocol
Summary of Contents for IQ 250
Page 2: ......
Page 22: ...3 6 IB02601006E www eaton com Chapter 3 Mechanical Installation IQ 250 260 Meter...
Page 38: ...4 16 IB2601006E www eaton com Chapter 4 Electrical Installation IQ 250 260 Meter...
Page 104: ...A 6 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter...
Page 134: ...A IQ 250 260 Meter Appendix B Modbus Mapping www eaton com IB02601006E MM 28...