Chapter 8:
IQ 250/260 Meter Programming the IQ 250/260
www.eaton.com
IB02601006E
8-19
b. Enter
Units/Count
. The Units/Count is the
output ratio
from the device that is being input into the
meter.
For example
, if you have a KYZ module that is outputting a pulse every 1.8 kWh, with the
input set to Accumulator, Increment on Contact Opening, you would set the Units/Count to be the value
of the KYZ; in this case either 1.8 or a ratio of that number.
NOTE
: When EOI is chosen for the Assigned to, a pulse is generated on the selected EOI Event.
When this option is chosen, you do not need to set
Units/Count
.
c. Enter
Compression
. The
Compression Factor
is used to adjust how high an accumulator will go
before rolling over. Because of this, it is useful for
delaying rollover
.
For example
, if you select a
Compression Factor of 10, each time 10 Pulse/State changes occur, the accumulator count will
increment by 1. The
available Compression Factors
are:
1, 10, 100, 1000, 10000
, and
100000
. The
default Compression Factor is 1.
d. Enter a
Label
for the
Accumulator
.
· The current Input Labels are displayed on
the screen. To change the Input Labels,
click in the Labels field you want to change,
and enter a new label.
Configuring a 0-1 mA Output Card (IQ250/260-IO3):
The
0-1mA Output Option Card
is an
analog communication card
, which transmits a standard, bi-directional 0-1
milliamp signal. For technical specifications and hardware installation, see Chapter 7 of this manual.
An
example use
of the optional 0-1mA Output Card is in enabling the meter to communicate with an RTU (Remote
Terminal Unit).
1. Click
0-1 mA Output
.
· You can set up to four Output IDs for your
Output Card.
2. Double-click an
Assigned Channel field
to
add
or
edit
an
Output ID
. You will see the window
shown on the next page.
Summary of Contents for IQ 250
Page 2: ......
Page 22: ...3 6 IB02601006E www eaton com Chapter 3 Mechanical Installation IQ 250 260 Meter...
Page 38: ...4 16 IB2601006E www eaton com Chapter 4 Electrical Installation IQ 250 260 Meter...
Page 104: ...A 6 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter...
Page 134: ...A IQ 250 260 Meter Appendix B Modbus Mapping www eaton com IB02601006E MM 28...