A
IQ 250/260 Meter
Appendix B:
Modbus Mapping
0411 - 0412
1042 - 1043
VAs, Phase A
FLOAT
-9999 M to +9999 M
VAs
2
0413 - 0414
1044 - 1045
VAs, Phase B
FLOAT
-9999 M to +9999 M
VAs
2
0415 - 0416
1046 - 1047
VAs, Phase C
FLOAT
-9999 M to +9999 M
VAs
2
0417 - 0418
1048 - 1049
Power Factor, Phase A
FLOAT
-1.00 to +1.00
none
2
0419 - 041A
1050 - 1051
Power Factor, Phase B
FLOAT
-1.00 to +1.00
none
2
041B - 041C
1052 - 1053
Power Factor, Phase C
FLOAT
-1.00 to +1.00
none
2
041D - 0425
1054 - 1062
Reserved
Reserved
9
Block Size:
63
read-only
05DB - 05DC
1500 - 1501
W-hours, Received
SINT32
0 to 99999999 or
0 to -99999999
Wh per energy format
2
05DD - 05DE
1502 - 1503
W-hours, Delivered
SINT32
0 to 99999999 or
0 to -99999999
Wh per energy format
2
05DF - 05E0
1504 - 1505
W-hours, Net
SINT32
-99999999 to 99999999
Wh per energy format
2
05E1 - 05E2
1506 - 1507
W-hours, Total
SINT32
0 to 99999999
Wh per energy format
2
05E3 - 05E4
1508 - 1509
VAR-hours, Positive
SINT32
0 to 99999999
VARh per energy format
2
05E5 - 05E6
1510 - 1511
VAR-hours, Negative
SINT32
0 to -99999999
VARh per energy format
2
05E7 - 05E8
1512 - 1513
VAR-hours, Net
SINT32
-99999999 to 99999999
VARh per energy format
2
05E9 - 05EA
1514 - 1515
VAR-hours, Total
SINT32
0 to 99999999
VARh per energy format
2
05EB - 05EC
1516 - 1517
VA-hours, Total
SINT32
0 to 99999999
VAh per energy format
2
05ED - 05EE
1518 - 1519
W-hours, Received, Phase A
SINT32
0 to 99999999 or 0 to -
99999999
Wh per energy format
2
05EF - 05F0
1520 - 1521
W-hours, Received, Phase B
SINT32
0 to 99999999 or
0 to -99999999
Wh per energy format
2
05F1 - 05F2
1522 - 1523
W-hours, Received, Phase C
SINT32
0 to 99999999 or
0 to -99999999
Wh per energy format
2
05F3 - 05F4
1524 - 1525
W-hours, Delivered, Phase A
SINT32
0 to 99999999 or
0 to -99999999
Wh per energy format
2
05F5 - 05F6
1526 - 1527
W-hours, Delivered, Phase B
SINT32
0 to 99999999 or
0 to -99999999
Wh per energy format
2
05F7 - 05F8
1528 - 1529
W-hours, Delivered, Phase C
SINT32
0 to 99999999 or
0 to -99999999
Wh per energy format
2
05F9 - 05FA
1530 - 1531
W-hours, Net, Phase A
SINT32
-99999999 to 99999999
Wh per energy format
2
05FB - 05FC
1532 - 1533
W-hours, Net, Phase B
SINT32
-99999999 to 99999999
Wh per energy format
2
05FD - 05FE
1534 - 1535
W-hours, Net, Phase C
SINT32
-99999999 to 99999999
Wh per energy format
2
05FF - 0600
1536 - 1537
W-hours, Total, Phase A
SINT32
0 to 99999999
Wh per energy format
2
0601 - 0602
1538 - 1539
W-hours, Total, Phase B
SINT32
0 to 99999999
Wh per energy format
2
0603 - 0604
1540 - 1541
W-hours, Total, Phase C
SINT32
0 to 99999999
Wh per energy format
2
0605 - 0606
1542 - 1543
VAR-hours, Positive, Phase A
SINT32
0 to 99999999
VARh per energy format
2
0607 - 0608
1544 - 1545
VAR-hours, Positive, Phase B
SINT32
0 to 99999999
VARh per energy format
2
0609 - 060A
1546 - 1547
VAR-hours, Positive, Phase C
SINT32
0 to 99999999
VARh per energy format
2
060B - 060C
1548 - 1549
VAR-hours, Negative, Phase A
SINT32
0 to -99999999
VARh per energy format
2
060D - 060E
1550 - 1551
VAR-hours, Negative, Phase B
SINT32
0 to -99999999
VARh per energy format
2
060F - 0610
1552 - 1553
VAR-hours, Negative, Phase C
SINT32
0 to -99999999
VARh per energy format
2
Primary Energy Block
* Wh received & delivered always have opposite signs
* Wh received is positive for "view as load", delivered is
positive for "view as generator"
* 5 to 8 digits
* decimal point implied, per energy format
* resolution of digit before decimal point = units, kilo, or
mega, per energy format
* see note 10
www.eaton.com
IB02601006E MM-2
Summary of Contents for IQ 250
Page 2: ......
Page 22: ...3 6 IB02601006E www eaton com Chapter 3 Mechanical Installation IQ 250 260 Meter...
Page 38: ...4 16 IB2601006E www eaton com Chapter 4 Electrical Installation IQ 250 260 Meter...
Page 104: ...A 6 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter...
Page 134: ...A IQ 250 260 Meter Appendix B Modbus Mapping www eaton com IB02601006E MM 28...