Chapter 8:
Programming the IQ 250/260 IQ 250/260 Meter
4. You can specify an
Accumulation Compression Factor.
The Compression Factor is used to adjust how high an
accumulator will go before rolling over. Because of this, it is useful in
delaying rollover.
For example
, if you select a Compression Factor of 10, each time 10 Pulse/State changes occur, the accumulator
count will increment by 1. The
available Compression Factors
are:
1, 10, 100, 1000, 10000
, and
100000
. The
default
Compression Factor is
1
.
5. To
configure
the
Relay Inputs
, click
Digital Input Settings
. Use this screen to set up
Accumulators
and
Input
Labels.
• You can set up to
two Input IDs
for your Relay
Card, and assign a
Label
,
Open
Label
, and
Closed
Label
for each.
• You can assign
labels
and other information for
Accumulators
for the Inputs.
a. Make a selection in the
Assigned to
field.
The
available selections
are:
• Status Only
• EOI Pulse, Trigger on Contact
Closing
• EOI Pulse, Trigger on Contact Opening
• EOI Pulse, Trigger on Contact Change
• Accumulator, Increment on Contact
Closing
• Accumulator, Increment on Contact Opening
• Accumulator, Increment on Contact Change
NOTES on End of Interval (EOI):
• EOI is triggered when the selected condition is met.
• EOI is used as a
trigger
for
demand averaging
: when the selected condition is met, the EOI delineates
an interval that results in demand averaging being performed.
• The minimum interval between EOI Pulses used to trigger demand averaging should be 5 minutes.
•
Only one Option Card input or output can be set to trigger an EOI pulse
.
b. Enter
Units/Count
. The Units/Count is the
output ratio
from the device that is being input into the meter.
For example
, if you have a KYZ module that is outputting a pulse every 1.8 kWh, with the input set to
Accumulator, Increment on Contact Opening, you would set the Units/Count to be the value of the KYZ; in
this case either 1.8 or a ratio of that number.
Summary of Contents for IQ 250
Page 2: ......
Page 22: ...3 6 IB02601006E www eaton com Chapter 3 Mechanical Installation IQ 250 260 Meter...
Page 38: ...4 16 IB2601006E www eaton com Chapter 4 Electrical Installation IQ 250 260 Meter...
Page 104: ...A 6 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter...
Page 134: ...A IQ 250 260 Meter Appendix B Modbus Mapping www eaton com IB02601006E MM 28...