Chapter 2:
Overview and Specifications IQ 250/260 Meter
Compliance
• UL Listing: USL/CNL E250818
• IEC 687 (0.2% Accuracy)
• ANSI C12.20 (0.2% Accuracy)
•
• ANSI C62.41 (Burst)
•
I C12.2
• IEC 1000-4-2 - ESD
•
ANSI C62.41 to be supplied before document release
Accuracy
(See full Range specifications earlier in this chapter.)
For 23
o
C, 3 Phase balanced Wye or Delta load, at 50 or 60 Hz (as per order), 5A (Class 10)
nominal unit:
Parameter
Accuracy
Accuracy Input Range1
Voltage L-N [V]
0.1% of reading
(69 to 480)V
Voltage L-L [V]
0.2% of reading
2
(120 to 600)V
Current Phase [A]
0.1% of reading
3
(0.15 to 5) A
Current Neutral (calculated)
[A]
2% of Full Scale
(0.15 to 5) A @ (45 to 65) Hz
Active Power Total [W]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to 480) V @ +/- (0.5 to 1) lag/lead PF
Active Energy Total [Wh]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to 480) V @ +/- (0.5 to 1) lag/lead PF
Reactive Power Total [VAR]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to 480) V @ +/- (0 to 0.8) lag/lead PF
Reactive Energy Total [VARh] 0.2% of reading
1, 2
(0.15 to 5) A @ (69 to 480) V @ +/- (0 to 0.8) lag/lead PF
Apparent Power Total [VA]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to 480) V @ +/- (0.5 to 1) lag/lead PF
Apparent Energy Total [VAh]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to 480) V @ +/- (0.5 to 1) lag/lead PF
Power Factor
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to 480) V @ +/- (0.5 to 1) lag/lead PF
Frequency [Hz]
+/- 0.03 Hz
(45 to 65) Hz
Total Harmonic Distortion [%] +/- 2%
(0.5 to 10)A
4
or (69 to 480)V, measurement range (1 to 99.99)%
Load Bar
+/- 1 segment
(0.005 to 6) A
1
• For 2.5 element programmed units, degrade accuracy by an additional 0.5% of reading.
• For 1A (Class 2) Nominal, degrade accuracy by an additional 0.5% of reading.
• For 1A (Class 2) Nominal, the input current range for accuracy specification is 20% of the values listed
in the table.
2
For unbalanced voltage inputs where at least one crosses the 150V autoscale threshold (for example,
120V/120V/208V system), degrade the accuracy to 0.4% of reading.
3
With reference voltage applied (VA, VB, or VC). Otherwise, degrade accuracy to 0.2%. See hookup
diagrams 8, 9, and 10 in Chapter 4.
4
At least one voltage input (minimum 20 Vac) must be connected for THD measurement on current
channels.
Summary of Contents for IQ 250
Page 2: ......
Page 22: ...3 6 IB02601006E www eaton com Chapter 3 Mechanical Installation IQ 250 260 Meter...
Page 38: ...4 16 IB2601006E www eaton com Chapter 4 Electrical Installation IQ 250 260 Meter...
Page 104: ...A 6 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter...
Page 134: ...A IQ 250 260 Meter Appendix B Modbus Mapping www eaton com IB02601006E MM 28...