A
IQ 250/260 Meter
Appendix B:
Modbus Mapping
read-only except as indicated
2B3F - 2B3F
11072 - 11072
Digital Input States
UINT16
bit-mapped
-------- 22221111
Two nibble fields: (2222) for input#2 and (1111) for input
#1.
Lsb in each nibble is the current state of the input. Msb in
each nibble is the oldest registered state.
1
2B40 - 2B40
11073 - 11073
Digital Relay States
UINT16
bit-mapped
-------- --ab--cd
If "a" is 1 then state of Relay#2 is unknown, otherwise state
of Relay#2 is informed in "c": (1=tripped, 0=released).
If "b" is 1 then state of Relay#1 is unknown, otherwise state
of Relay#1 is informed in "d": (1=tripped, 0=released).
1
2B41 - 2B41
11074 - 11074
Turn relay on
UINT16
bit-mapped
-------- ------21
Writing a 1 in bit N turns relay N+1 ON (this register is
writeable only in privileged session).
1
2B42 - 2B42
11075 - 11075
Turn relay off
UINT16
bit-mapped
-------- ------21
Writing a 1 in bit N turns relay N+1 OFF (this register is
writeable only in privileged session).
1
2B43 - 2B43
11076 - 11076
Trip/Release delay timer for Relay 1
UINT16
0 to 9999
0.1 sec
Time to trip or release.
1
2B44 - 2B44
11077 - 11077
Trip/Release delay timer for Relay 2
UINT16
0 to 9999
0.1 sec
Time to trip or release.
1
2B45 - 2B46
11078 - 11079
Reserved
Reserved
2
2B47 - 2B47
11080 - 11080
Input 1 Accumulator, Scaled
UINT16
0 to 9999
1
2B48 - 2B48
11081 - 11081
Input 2 Accumulator, Scaled
UINT16
0 to 9999
1
2B49 - 2B4A
11082 - 11083
Reserved
Reserved
2
2B4B - 2B4B
11084 - 11084
Relay 1 Accumulator, Scaled
UINT16
0 to 9999
1
2B4C - 2B4C
11085 - 11085
Relay 2 Accumulator, Scaled
UINT16
0 to 9999
1
2B4D - 2B78
11086 - 11129
Reserved
Reserved
44
Block Size:
58
15)
read-only except as indicated
2B3F - 2B3F
11072 - 11072
Digital Input States
UINT16
bit-mapped
dddd cccc bbbb aaaa
Nibble "dddd" for input#4, "cccc" for input#3, "bbbb" for
input#2 and "aaaa" for input#1.
Within each field, rightmost bit is the current state
(1=closed, 0=open), and bits at left are the older states
100ms apart (historical states).
Example:
xxxx xxxx xxxx 0011
Current state of input#1 is closed, before that it was closed
too, before that it was open and the oldest state known is
open.
1
2B40 - 2B40
11073 - 11073
Digital Output States
UINT16
bit-mapped
-------- ----4321
One bit for each output. Bit 4 is for output #4, and bit 1 is for
output #1. If a bit is set the output is closed, otherwise it is
opened.
1
2B41 - 2B41
11074 - 11074
Pulse Output Test Select
UINT16
bit-mapped
-------- ----4321
Writing 1 in bit N sets Pulse Output N+1 in test mode.
Writing 0 otherwise, reestablished the output in normal
operation (only while in privileged session).
When Reading this reports which Pulse Output is under test
according to the bits set or cleared (1=under test,
0=normal).
1
Expansions for Data and Control Block for Option Card 2
Data and Control Block --
Digital I/O Relay Card Overlay (Note 15)
resolution is 1, 10, 100, 1000,
10000, or 100000 counts
Disabled accumulators always read 0.
Data and Control Block --
Digital I/O Pulse Output Card Overlay (Note 15)
resolution is 1, 10, 100, 1000,
10000, or 100000 counts
Disabled accumulators always read 0.
www.eaton.com
IB02601006E MM-14
Summary of Contents for IQ 250
Page 2: ......
Page 22: ...3 6 IB02601006E www eaton com Chapter 3 Mechanical Installation IQ 250 260 Meter...
Page 38: ...4 16 IB2601006E www eaton com Chapter 4 Electrical Installation IQ 250 260 Meter...
Page 104: ...A 6 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter...
Page 134: ...A IQ 250 260 Meter Appendix B Modbus Mapping www eaton com IB02601006E MM 28...