Chapter 6:
IQ 250/260 Meter Using the IQ 250/260
www.eaton.com
IB02601006E
6-5
Using Configuration Mode
Configuration Mode
follows Reset: Energy on the Main Menu.
To access
Configuration Mode
:
1. Press the
Menu
button while the meter is auto-scrolling parameters.
2. Press the
Down
button until the Configuration Mode option (
CFG
) is in the A window.
3. Press the
Enter
button. The
Configuration Parameters
screen appears.
4. Press the
Down
button to scroll through the configuration parameters:
Scroll (SCrL)
,
CT
,
PT
,
Connection
(Cnct)
and
Port
. The parameter currently ‘Active,” i.e., configurable, flashes in the A window.
5. Press the
Enter
button to access the Setting screen for the currently active parameter.
NOTE
:
You can use the Enter button to scroll through all of the Configuration parameters and their
Setting screens, in order.
Press
Enter
when CFG is in A window - Parameter screen appears - Press
Down
-
Press
Enter
when Parameter you want is in A window
6. The parameter screen appears, showing the current settings. To change the settings:
• Use either the
Down
button or the
Right
button to select an option.
• To enter a number value, use the
Down
button to select the number value for a digit and the
Right
button
to move to the next digit.
NOTE:
When you try to change the current setting and Password Protection is enabled for the meter, the
Password screen appears.
See the previous page for instructions on entering a password
.
7. Once you have entered the new setting, press the
Menu
button twice.
8. The
Store ALL YES
screen appears. You can either:
• Press the
Enter
button to
save
the new setting.
• Press the
Right
button to access the
Store ALL no
screen; then press the Enter button to
cancel
the Save.
9. If you have saved the settings, the
Store ALL done
screen appears and the meter resets.
Press the Enter button to save the settings Press the Enter button to The settings have been saved
Summary of Contents for IQ 250
Page 2: ......
Page 22: ...3 6 IB02601006E www eaton com Chapter 3 Mechanical Installation IQ 250 260 Meter...
Page 38: ...4 16 IB2601006E www eaton com Chapter 4 Electrical Installation IQ 250 260 Meter...
Page 104: ...A 6 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter...
Page 134: ...A IQ 250 260 Meter Appendix B Modbus Mapping www eaton com IB02601006E MM 28...