A X - 3 S e r i e s O p e r a t i o n M a n u a l
7 - 1 0 2
_7
Then choose the corresponding interrupt contact from the drop down list of External event.
The setting value for hardware filter time is smaller than IN input duty on time as shown below:
The input range for hardawre filter is from 0 to 50,000,000, unit as 0.01
μ
s
The relation between filter frequency and filter time:
Filter frequency*
1
(Hz): Filter frequency= 1 / (2*t); t is the filter time setting value (unit:
0.01μ
s). When input
frequency is higher than the filter frequency range, signals are filtered.
The function focuses on the X input point used in DFB_Capture, DFB_Hcnt, DFB_HTmr, DFB_Compare and
IO interrupt.