C h a p t e r 2 Sp e c i f i c a t i o n s a n d S y s t e m C o n f i g u r a t i o
n s
2 - 2
2_
2.1
General Specifications
Item
Specifications
Operating temperature
-20 to 55°C*
1
Storage temperature
-40 to 80°C
Operating humidity
5–95%
No condensation
Storage humidity
5–95%
No condensation
Work environment
No corrosive gas exists.
Installation location
In a control box
Pollution degree
2
Ingress protection
(IP ratings)
IP20
EMC Standard
(electromagnetic
compatibility)
Refer to tables of EMI, EMS and conducted immunity test below.
Vibration resistance
Tested with:
5 Hz
≦
f
≦
8.4 Hz, constant amplitude 3.5 mm;
8.4 Hz
≦
f
≦
150 Hz, constant acceleration 1g
Duration of oscillation: 10 sweep cycles
per axis on each direction of the three mutually perpendicular axes
International Standard IEC 61131-2 & IEC 60068-2-6 (TEST Fc)
Shock resistance
Tested with:
Half-sine wave:
Strength of shock 15 g peak value, 11 ms duration;
Shock direction: The shocks in each in direction per axis, on three mutually
perpendicular axes (total of 18 shocks)
International Standard IEC 61131-2 & IEC 60068-2-27 (TEST Ea)
Safety
Conforms to IEC 61131-2, UL508
Ambient air
temperature-barometric
pressure-altitude
Operating: 1080 ~ 795hPa (-1000 ~ 2000 m)
Storage:1080 ~ 660hPa (-1000 ~ 3500 m)
*1: Leave the AX-3 Series PLC in an environment within the operating temperature for at least one hour to
ensure the AX-3 Series PLC temperature is within the operating temperature.
•
EMI
Port
Frequency range
Level (Normative)
Reference standard
Enclosure port
(radiated)
(measured at a distance of
10 meters)
30-230 MHz
40 dB (
μV/m
) quasi-peak
IEC 61000-6-4
230-1000 MHz
47 dB (
μV/m
) quasi-peak
AC power port
(conducted)
0.15-0.5 MHz
79 dB (
μV
) quasi-peak
IEC 61000-6-4
66 dB (
μV
) average
0.5-30 MHz
73 dB (
μV
) quasi-peak
60 dB (
μV
) average
Summary of Contents for AX-3 Series
Page 17: ...AX 3 Series Operation Manual 1 10 _1 MEMO...
Page 54: ...AX 3 Series Operation Manual 3 22 _3 MEMO...
Page 98: ...AX 3 Series Operation Manual 4 44 _4 MEMO...
Page 118: ...AX 3 Series Operation Manual 6 8 _6 MEMO...
Page 310: ...AX 3 Series Operation Manual 8 18 8_ MEMO...
Page 355: ...Appendix A Troubleshooting A 5 _A...