Troubleshooting by Indication on the Unified ON/OFF Control
Troubleshooting
191
Cannot be used in
combination with a wiring
adapter for electrical
appendices. Remove the
wiring adapter for electrical
appendices and reset the
power supply for all optional
controllers for centralized
control simultaneously.
Schedule timer and data
station cannot be used in
combination. Disconnect
either the schedule timer or
data station and reset the
power supply for all optional
controls for centralized control
simultaneously.
Schedule timer and parallel
interface cannot be used in
combination. Disconnect
either the schedule timer or
parallel interface and reset the
power supply for all optional
controls for centralized control
simultaneously.
Disconnect the schedule
timer's individual / combined
connector and reset the power
supply for all optional controls
for centralized control
simultaneously.
Arrange so that the connector
for setting master control is
connected to one control for
centralized control and reset
the power supply for all
optional controls for
centralized control
simultaneously.
Disconnect the connector for
setting master control from
the master control, connect to
another optional control for
centralized control and
simultaneously reset all
optional controls for
centralized control again. The
controller connected by the
connector for setting master
control when the malfunction
is cleared is defective and
must be replaced.
Reset the power supply for
all optional controllers for
centralized control
simultaneously.
Is the wiring adapter for
electrical appendices
connected?
Is a schedule timer
connected?
Are there
two or more
optional controls for
centralized control connected
with the connector for
setting master
control?
Is a parallel interface
connected?
Is a data station
connected?
2A
(V2843)
Is the schedule timer's
individual/combined connector
connected?
If the malfunction is still not cleared:
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
Summary of Contents for VRVIII-S
Page 1: ...SiENBE34 703 Basic Training Manual R 410A Heat Pump 50Hz Service Manual...
Page 11: ...Introduction SiENBE34 703 x...
Page 113: ...Field Setting SiENBE34 703 102 Test Operation...
Page 207: ...Troubleshooting by Indication on the Unified ON OFF Control SiENBE34 703 196 Troubleshooting...
Page 215: ...Wiring Diagrams SiENBE34 703 204 Appendix 2 3 Indoor Unit FXCQ20 25 32 63M8...
Page 216: ...SiENBE34 703 Wiring Diagrams Appendix 205 FXCQ40 50 80 125M8V3...
Page 217: ...Wiring Diagrams SiENBE34 703 206 Appendix FXFQ25 32 40 50 63 80 100 125P7VE...
Page 218: ...SiENBE34 703 Wiring Diagrams Appendix 207 FXZQ20 25 32 40 50M8V1...
Page 221: ...Wiring Diagrams SiENBE34 703 210 Appendix FXDQ20 25M8V3...
Page 222: ...SiENBE34 703 Wiring Diagrams Appendix 211 FXSQ20 25 32 40 50 63 80 100 125M8V3...
Page 232: ...SiENBE34 703 Option List Appendix 221...
Page 235: ...Example of Connection SiENBE34 703 224 Appendix...
Page 241: ...Method of Replacing the Inverter s Power Transistors Modules SiBE34 703 230 Appendix...
Page 261: ...RXYSQ4 5 6 P7Y1B SiENBE34 703 250 Removal Procedure...