SiENBE34-703
Field Setting
Test Operation
95
3.2.3 Setting of Low Noise Operation and Demand Operation
Setting of Low Noise Operation
By connecting the external contact input to the low noise input of the outdoor unit external
control adapter (optional), you can lower operating noise by 2-3 dB.
When the low noise operation is carried out automatically at night (The external control
adapter for outdoor unit is not required)
1. While in "Setting mode 2", select the setting condition (i.e., "Mode 1", "Mode 2", or "Mode 3")
for set item No. 22 (Setting of nighttime low noise level).
2. If necessary, while in "Setting mode 2", select the setting condition (i.e., "20:00", "22:00", or
"24:00") for set item No. 26 (Setting of start time of nighttime low noise operation).
(Use the start time as a guide since it is estimated according to outdoor temperatures.)
3. If necessary, while in "Setting mode 2", select the setting condition (i.e., "06:00", "07:00", or
"08:00") for set item No. 27 (Setting of end time of nighttime low noise operation).
(Use the end time as a guide since it is estimated according to outdoor temperatures.)
4. If necessary, while in "Setting mode 2", set the setting condition for set item No. 29 (Setting
of capacity precedence) to "ON".
(If the condition is set to "ON", when the air-conditioning load reaches a high level, the
system will be put into normal operation mode even during nighttime.)
Image of operation
(V3079)
Operation sound
Rated operation
sound
Operation sound
of mode 1
Operation sound
of mode 2
Operation sound
of mode 3
If capacity precedence is set in "Capacity
precedence setting", the fan speed will be
increased according to the load of air
conditioning when load is heavier.
Time set with "Night-time low noise start setting"
Time set with "Night-time low noise end setting"
Set with "Night-time low noise start setting"
(Factory setting is "PM 10:00".)
Set with "Night-time low noise end setting"
(Factory setting is "PM 8:00".)
Operation sound during
night-time low noise mode is
instructed can be set with
"Night-time low noise level
setting".
(Factory setting is "OFF".)
Operation sound level set with
"Night-time low noise setting”
Night time
PM 8:00
PM 10:00
PM 0:00
AM 8:00
AM 7:00
AM 8:00
Summary of Contents for VRVIII-S
Page 1: ...SiENBE34 703 Basic Training Manual R 410A Heat Pump 50Hz Service Manual...
Page 11: ...Introduction SiENBE34 703 x...
Page 113: ...Field Setting SiENBE34 703 102 Test Operation...
Page 207: ...Troubleshooting by Indication on the Unified ON OFF Control SiENBE34 703 196 Troubleshooting...
Page 215: ...Wiring Diagrams SiENBE34 703 204 Appendix 2 3 Indoor Unit FXCQ20 25 32 63M8...
Page 216: ...SiENBE34 703 Wiring Diagrams Appendix 205 FXCQ40 50 80 125M8V3...
Page 217: ...Wiring Diagrams SiENBE34 703 206 Appendix FXFQ25 32 40 50 63 80 100 125P7VE...
Page 218: ...SiENBE34 703 Wiring Diagrams Appendix 207 FXZQ20 25 32 40 50M8V1...
Page 221: ...Wiring Diagrams SiENBE34 703 210 Appendix FXDQ20 25M8V3...
Page 222: ...SiENBE34 703 Wiring Diagrams Appendix 211 FXSQ20 25 32 40 50 63 80 100 125M8V3...
Page 232: ...SiENBE34 703 Option List Appendix 221...
Page 235: ...Example of Connection SiENBE34 703 224 Appendix...
Page 241: ...Method of Replacing the Inverter s Power Transistors Modules SiBE34 703 230 Appendix...
Page 261: ...RXYSQ4 5 6 P7Y1B SiENBE34 703 250 Removal Procedure...