SiENBE34-703
Troubleshooting by Indication on the remote control
Troubleshooting
151
3.24
“
J5
”
Outdoor Unit: Malfunction of Thermistor (R3T, R5T)
for Suction Pipe 1, 2
remote control
Display
J5
Applicable
Models
RXYSQ4~6P
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the thermistor for suction pipe 1, 2.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the thermistor for suction pipe 1, 2 are detected.
Supposed
Causes
!
Defect of thermistor (R3T, R5T) for outdoor unit suction pipe
!
Defect of outdoor unit PC board (A1P)
Troubleshooting
∗
Refer to thermistor resistance / temperature characteristics table on P225.
(V3073)
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Caution
Replace outdoor unit PC board
(A1P).
Connect the thermistor and turn
on again.
Replace the thermistor (R3T, R5T).
Connector of the
thermistor for suction
pipe1, 2 is connected to
X12A of outdoor unit
PC board
(A1P).
Resistance is
normal when
measured after
disconnecting the thermistor
(R3T, R5T) from the
outdoor unit PC board.
(3.5k
Ω
~360k
Ω
)
YES
YES
NO
NO
Summary of Contents for VRVIII-S
Page 1: ...SiENBE34 703 Basic Training Manual R 410A Heat Pump 50Hz Service Manual...
Page 11: ...Introduction SiENBE34 703 x...
Page 113: ...Field Setting SiENBE34 703 102 Test Operation...
Page 207: ...Troubleshooting by Indication on the Unified ON OFF Control SiENBE34 703 196 Troubleshooting...
Page 215: ...Wiring Diagrams SiENBE34 703 204 Appendix 2 3 Indoor Unit FXCQ20 25 32 63M8...
Page 216: ...SiENBE34 703 Wiring Diagrams Appendix 205 FXCQ40 50 80 125M8V3...
Page 217: ...Wiring Diagrams SiENBE34 703 206 Appendix FXFQ25 32 40 50 63 80 100 125P7VE...
Page 218: ...SiENBE34 703 Wiring Diagrams Appendix 207 FXZQ20 25 32 40 50M8V1...
Page 221: ...Wiring Diagrams SiENBE34 703 210 Appendix FXDQ20 25M8V3...
Page 222: ...SiENBE34 703 Wiring Diagrams Appendix 211 FXSQ20 25 32 40 50 63 80 100 125M8V3...
Page 232: ...SiENBE34 703 Option List Appendix 221...
Page 235: ...Example of Connection SiENBE34 703 224 Appendix...
Page 241: ...Method of Replacing the Inverter s Power Transistors Modules SiBE34 703 230 Appendix...
Page 261: ...RXYSQ4 5 6 P7Y1B SiENBE34 703 250 Removal Procedure...