SiENBE34-703
Troubleshooting by Indication on the remote control
Troubleshooting
179
3.47
“
UF
”
System is not Set yet
remote control
Display
UF
Applicable
Models
All models of indoor units
RXYSQ4~6P
Method of
Malfunction
Detection
On check operation, the number of indoor units in terms of transmission is not corresponding to
that of indoor units that have made changes in temperature.
Malfunction
Decision
Conditions
The malfunction is determined as soon as the abnormality aforementioned is detected through
checking the system for any erroneous connection of units on the check operation.
Supposed
Causes
!
Improper connection of transmission wiring between indoor-outdoor units and outdoor-
outdoor units
!
Failure to execute check operation
!
Defect of indoor unit PC board
!
Stop valve is left in closed
Troubleshooting
Note:
Wiring check operation may not be successful if carried out after the outdoor unit has been off
for more than 12 hours, or if it is not carried out after running all connected indoor units in the
fan mode for at least an hour.
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(V2830)
Caution
Is
indoor - outdoor
and outdoor - outdoor unit
transmission wiring
normal?
Replace indoor unit PC board.
Wiring check operation may
not have been carried out
successfully.
After fixing incorrect wiring,
push and hold the RESET
button on the master outdoor
unit PC board for 5 seconds.
* The unit will not run for up to
12 minutes.
Is the check
operation carried
out?
Is indoor
-outdoor and outdoor-
outdoor unit transmission
wiring normal?
Open stop valve.
Are the stop valves
opened?
YES
YES
YES
YES
NO
NO
NO
NO
Summary of Contents for VRVIII-S
Page 1: ...SiENBE34 703 Basic Training Manual R 410A Heat Pump 50Hz Service Manual...
Page 11: ...Introduction SiENBE34 703 x...
Page 113: ...Field Setting SiENBE34 703 102 Test Operation...
Page 207: ...Troubleshooting by Indication on the Unified ON OFF Control SiENBE34 703 196 Troubleshooting...
Page 215: ...Wiring Diagrams SiENBE34 703 204 Appendix 2 3 Indoor Unit FXCQ20 25 32 63M8...
Page 216: ...SiENBE34 703 Wiring Diagrams Appendix 205 FXCQ40 50 80 125M8V3...
Page 217: ...Wiring Diagrams SiENBE34 703 206 Appendix FXFQ25 32 40 50 63 80 100 125P7VE...
Page 218: ...SiENBE34 703 Wiring Diagrams Appendix 207 FXZQ20 25 32 40 50M8V1...
Page 221: ...Wiring Diagrams SiENBE34 703 210 Appendix FXDQ20 25M8V3...
Page 222: ...SiENBE34 703 Wiring Diagrams Appendix 211 FXSQ20 25 32 40 50 63 80 100 125M8V3...
Page 232: ...SiENBE34 703 Option List Appendix 221...
Page 235: ...Example of Connection SiENBE34 703 224 Appendix...
Page 241: ...Method of Replacing the Inverter s Power Transistors Modules SiBE34 703 230 Appendix...
Page 261: ...RXYSQ4 5 6 P7Y1B SiENBE34 703 250 Removal Procedure...