Troubleshooting by Remote Control
SiENBE34-703
118
Troubleshooting
Malfunction code indication by outdoor unit PC board
To enter the monitor mode, push the
MODE (BS1) button when in “Setting
mode 1”.
Push the SET (BS2) button and set
the LED display to a setting item.
Push the RETURN (BS3) button
once to display "First digit" of
malfunction code.
Push the SET (BS2) button once to
display "Second digit" of malfunction
code.
Push the RETURN (BS3) button and
switches to the initial status of
“Monitor mode”.
* Push the MODE (BS1) button and
returns to “Setting mode 1”.
Push the SET (BS2) button once to
display "malfunction location".
Detail
description
on next
page.
Push the SET (BS2) button once to
display "master or slave 1 or slave 2"
and "malfunction location".
<Confirmation of malfunction 4>
<Confirmation of malfunction 3>
<Confirmation of malfunction 2>
<Confirmation of malfunction 1>
<Selection of setting item>
<Monitor mode>
Contents of malfunction
Malfunction
code
In-phase malfunction of DIII Net
Detection of DIII Net
E1
Abnormal discharge pressure
HPS activated
E3
Abnormal suction pressure
Abnormal Pe
E4
Compressor lock
Detection of INV compressor lock
E5
Over load, over current,
abnormal lock of outdoor unit fan motor
Detection of DC fan 1 motor lock
E7
Detection of DC fan 2 motor lock
Malfunction of electronic expansion
valve
EV1
E9
EV3
Faulty sensor of outdoor air
temperature
Faulty Ta sensor (short)
H9
Abnormal discharge pipe temperature
Abnormal Td
F3
Abnormal heat exchanger temperature Refrigerant over charge
F6
Faulty sensor of discharge pipe
temperature
Faulty Tdi sensor (short)
J3
Faulty sensor of suction pipe
temperature
Faulty Ts1 sensor (short)
J5
Faulty Ts2 sensor (short)
Faulty sensor of heat exchanger
temperature
Faulty Tb sensor (short)
J6
Malfunction of the liquid pipe
temperature sensor
Faulty TI sensor (short)
J7
Faulty sensor of subcool heat
exchanger temperature
Faulty Tsh sensor (short)
J9
Faulty sensor of discharge pressure
Faulty Pc sensor (short)
JA
Faulty sensor of suction pressure
Faulty Pe sensor (short)
JC
Faulty Inverter PC board
Faulty IPM
L1
Abnormal Current sensor offset
Abnormal IGBT
Faulty Current sensor
Abnormal SP-PAM over-voltage
Inverter radiation fin temperature rising Over heating of inverter radiation fin temperature
L4
DC output over current
Inverter instantaneous over current
L5
Electronic thermal
Electronic thermal switch 1
L8
Electronic thermal switch 2
Out-of-step
Speed down after startup
Lightening detection
Stall prevention (Limit time)
Stall prevention (Current increasing)
L9
Stall prevention (Faulty start up)
Abnormal wave form in startup
Out-of-step
Transmission error between inverter
and outdoor unit
Inverter transmission error
LC
Summary of Contents for VRVIII-S
Page 1: ...SiENBE34 703 Basic Training Manual R 410A Heat Pump 50Hz Service Manual...
Page 11: ...Introduction SiENBE34 703 x...
Page 113: ...Field Setting SiENBE34 703 102 Test Operation...
Page 207: ...Troubleshooting by Indication on the Unified ON OFF Control SiENBE34 703 196 Troubleshooting...
Page 215: ...Wiring Diagrams SiENBE34 703 204 Appendix 2 3 Indoor Unit FXCQ20 25 32 63M8...
Page 216: ...SiENBE34 703 Wiring Diagrams Appendix 205 FXCQ40 50 80 125M8V3...
Page 217: ...Wiring Diagrams SiENBE34 703 206 Appendix FXFQ25 32 40 50 63 80 100 125P7VE...
Page 218: ...SiENBE34 703 Wiring Diagrams Appendix 207 FXZQ20 25 32 40 50M8V1...
Page 221: ...Wiring Diagrams SiENBE34 703 210 Appendix FXDQ20 25M8V3...
Page 222: ...SiENBE34 703 Wiring Diagrams Appendix 211 FXSQ20 25 32 40 50 63 80 100 125M8V3...
Page 232: ...SiENBE34 703 Option List Appendix 221...
Page 235: ...Example of Connection SiENBE34 703 224 Appendix...
Page 241: ...Method of Replacing the Inverter s Power Transistors Modules SiBE34 703 230 Appendix...
Page 261: ...RXYSQ4 5 6 P7Y1B SiENBE34 703 250 Removal Procedure...