Field Setting
SiENBE34-703
88
Test Operation
The numbers in the "No." column represent the number of times to press the
SET (BS2) button.
No.
Setting item
Description
1
Cool/heat unified
address
Sets address for cool/heat unified operation.
2
Low noise/demand
address
Address for low noise/demand operation
3
Test operation
settings
Used to conduct test operation without making changes
to the PCB and replacing the refrigerant, after the
completion of maintenance.
5
Indoor unit forced
fan H
Allows forced operation of indoor unit fan while unit is
stopped. (H tap)
6
Indoor unit forced
operation
Allows forced operation of indoor unit.
8
Te setting
Target evaporation temperature for cooling
9
Tc setting
Target condensation temperature for heating
10 Defrost changeover
setting
Changes the temperature condition for defrost and sets to
quick defrost or slow defrost.
12
External low noise
setting / Demand
setting
Reception of external low noise or demand signal
13 AIRNET address
Set address for AIRNET.
16 Setting of hot water Make this setting to conduct heating operation with hot
water heater.
20
Additional
refrigerant charge
operation setting
Carries out additional refrigerant charge operation.
21
Refrigerant
recovery /
vacuuming mode
setting
Sets to refrigerant recovery or vacuuming mode.
22 Night-time low
noise setting
Sets automatic nighttime low noise operation in a simple
way.
The operating time is based on “Starting set” and “Ending
set”.
25 Setting of external
low noise level
Sets low noise level when the low noise signal is input
from outside.
26
Night-time low
noise operation
start setting
Sets starting time of nighttime low noise operation.
(Night-time low noise setting is also required.)
27
Night-time low
noise operation end
setting
Sets ending time of nighttime low noise operation.
(Night-time low noise setting is also required.)
28
Power transistor
check mode
∗
Check after
disconnection of
compressor wires
Used for trouble diagnosis of DC compressor. Since the
waveform of inverter is output without wiring to the
compressor, it is convenient to probe whether the trouble
comes from the compressor or PC board.
29 Capacity
precedence setting
If the capacity control is required, the low noise control is
automatically released by this setting during carrying out
low noise operation and nighttime low noise operation.
30 Demand setting 1
Changes target value of power consumption when
demand control 1 is input.
32 Normal demand
setting
Normally enables demand control 1 without external
input. (Effective to prevent a problem that circuit breaker
of small capacity is shut down due to large load.)
Push and hold the MODE (BS1)
button for 5 seconds and set to
“Setting mode 2”.
Push the SET (BS2) button and set
the LED display to a setting item
shown in the table on the right.
↓
Push the RETURN (BS3) button and
decide the item. (The present setting
condition is blinked.)
Push the SET (BS2) button and set
to the setting condition you want.
↓
Push the RETURN (BS3) button and
decide the condition.
Push the RETURN (BS3) button and
set to the initial status of “Setting
mode 2”.
* If you become unsure of how to
proceed, push the MODE (BS1)
button and return to setting mode 1.
(V2764)
b. “Setting mode 2”
<Selection of setting items>
<Selection of setting conditions>
Summary of Contents for VRVIII-S
Page 1: ...SiENBE34 703 Basic Training Manual R 410A Heat Pump 50Hz Service Manual...
Page 11: ...Introduction SiENBE34 703 x...
Page 113: ...Field Setting SiENBE34 703 102 Test Operation...
Page 207: ...Troubleshooting by Indication on the Unified ON OFF Control SiENBE34 703 196 Troubleshooting...
Page 215: ...Wiring Diagrams SiENBE34 703 204 Appendix 2 3 Indoor Unit FXCQ20 25 32 63M8...
Page 216: ...SiENBE34 703 Wiring Diagrams Appendix 205 FXCQ40 50 80 125M8V3...
Page 217: ...Wiring Diagrams SiENBE34 703 206 Appendix FXFQ25 32 40 50 63 80 100 125P7VE...
Page 218: ...SiENBE34 703 Wiring Diagrams Appendix 207 FXZQ20 25 32 40 50M8V1...
Page 221: ...Wiring Diagrams SiENBE34 703 210 Appendix FXDQ20 25M8V3...
Page 222: ...SiENBE34 703 Wiring Diagrams Appendix 211 FXSQ20 25 32 40 50 63 80 100 125M8V3...
Page 232: ...SiENBE34 703 Option List Appendix 221...
Page 235: ...Example of Connection SiENBE34 703 224 Appendix...
Page 241: ...Method of Replacing the Inverter s Power Transistors Modules SiBE34 703 230 Appendix...
Page 261: ...RXYSQ4 5 6 P7Y1B SiENBE34 703 250 Removal Procedure...