Special Control
SiENBE34-703
46
Function
3.2 Oil Return Operation
In order to prevent the compressor from running out of oil, the oil return operation is conducted to recover oil flown out
from the compressor to the system side.
3.2.1 Oil Return Operation in Cooling Operation
[Start conditions]
Referring to the set conditions for the following items, start the oil return operation in cooling.
• Cumulative oil feed rate
• Timer setting (Make this setting so as to start the oil return operation when the initial cumulative operating time
reaches two hours after power supply is turned ON and then every eight hours.)
Furthermore, the cumulative oil feed rate is computed from Tc, Te, and compressor loads.
Outdoor unit actuator
Oil return preparation
operation
Oil return operation
Post-oil-return operation
Compressor
Take the current step as the
upper limit.
52 Hz Full load
(
→
Low pressure constant
control)
Same as the
“
oil return
operation
”
mode.
Outdoor unit fan
Fan control (Normal cooling) Fan control (Normal cooling) Fan control (Normal cooling)
Four way valve
OFF
OFF
OFF
Main electronic expansion valve
(EV1)
480 pls
480 pls
480 pls
Subcooling electronic expansion
valve (EV3)
SH control
0 pls
0 pls
Hot gas bypass valve (SVP)
OFF
OFF
OFF
Ending conditions
20 sec.
•
3 min.
•
Ts - Te<5
°
C
•
3 min.
•
Pe<0.6MPa
•
HTdi>110
°
C
or
Indoor unit actuator
Cooling oil return operation
Fan
Thermostat ON unit
remote control setting
Stopping unit
OFF
Thermostat OFF unit
remote control setting
Electronic expansion valve
Thermostat ON unit
Normal opening
Stopping unit
224 pls
Thermostat OFF unit
Normal opening with forced thermostat ON
or
Summary of Contents for VRVIII-S
Page 1: ...SiENBE34 703 Basic Training Manual R 410A Heat Pump 50Hz Service Manual...
Page 11: ...Introduction SiENBE34 703 x...
Page 113: ...Field Setting SiENBE34 703 102 Test Operation...
Page 207: ...Troubleshooting by Indication on the Unified ON OFF Control SiENBE34 703 196 Troubleshooting...
Page 215: ...Wiring Diagrams SiENBE34 703 204 Appendix 2 3 Indoor Unit FXCQ20 25 32 63M8...
Page 216: ...SiENBE34 703 Wiring Diagrams Appendix 205 FXCQ40 50 80 125M8V3...
Page 217: ...Wiring Diagrams SiENBE34 703 206 Appendix FXFQ25 32 40 50 63 80 100 125P7VE...
Page 218: ...SiENBE34 703 Wiring Diagrams Appendix 207 FXZQ20 25 32 40 50M8V1...
Page 221: ...Wiring Diagrams SiENBE34 703 210 Appendix FXDQ20 25M8V3...
Page 222: ...SiENBE34 703 Wiring Diagrams Appendix 211 FXSQ20 25 32 40 50 63 80 100 125M8V3...
Page 232: ...SiENBE34 703 Option List Appendix 221...
Page 235: ...Example of Connection SiENBE34 703 224 Appendix...
Page 241: ...Method of Replacing the Inverter s Power Transistors Modules SiBE34 703 230 Appendix...
Page 261: ...RXYSQ4 5 6 P7Y1B SiENBE34 703 250 Removal Procedure...