Basic Control
SiENBE34-703
44
Function
2.4 Cooling Operation Fan Control
In cooling operation with low outdoor air temperature, this control is used to provide the
adequate amount of circulation air with liquid pressure secured by high pressure control using
outdoor unit fan.
Furthermore, when outdoor temperature
≥
20°C, the compressor will run in Step 7 or higher.
When outdoor temperature
≥
18°C, it will run in Step 5 or higher.
When outdoor temperature
≥
12°C, it will run in Step 1 or higher.
Fan Steps
Cooling
STEP0
STEP1
STEP2
STEP3
STEP4
STEP5
STEP6
STEP7
STEP8
M1F
0rpm
250rpm
400rpm
285rpm
360rpm
445rpm
580rpm
715rpm
850rpm
M2F
0 rpm
0 rpm
0 rpm
250 rpm
325rpm
410 rpm
545 rpm
680 rpm
815 rpm
Upper limit of fan
revolutions: Step 8
-1 step on
outdoor unit fan
+1 step on
outdoor unit fan
Pc
<2.75MPa
Pc
>3.24MPa
Lapse of 20 sec.
Hold the
current step on
outdoor unit fan
Upper limit of outdoor unit
fan revolutions
Step 7
PI control
PI control
Lapse of 20 sec.
PI control
Pc: HP pressure sensor detection value
Summary of Contents for VRVIII-S
Page 1: ...SiENBE34 703 Basic Training Manual R 410A Heat Pump 50Hz Service Manual...
Page 11: ...Introduction SiENBE34 703 x...
Page 113: ...Field Setting SiENBE34 703 102 Test Operation...
Page 207: ...Troubleshooting by Indication on the Unified ON OFF Control SiENBE34 703 196 Troubleshooting...
Page 215: ...Wiring Diagrams SiENBE34 703 204 Appendix 2 3 Indoor Unit FXCQ20 25 32 63M8...
Page 216: ...SiENBE34 703 Wiring Diagrams Appendix 205 FXCQ40 50 80 125M8V3...
Page 217: ...Wiring Diagrams SiENBE34 703 206 Appendix FXFQ25 32 40 50 63 80 100 125P7VE...
Page 218: ...SiENBE34 703 Wiring Diagrams Appendix 207 FXZQ20 25 32 40 50M8V1...
Page 221: ...Wiring Diagrams SiENBE34 703 210 Appendix FXDQ20 25M8V3...
Page 222: ...SiENBE34 703 Wiring Diagrams Appendix 211 FXSQ20 25 32 40 50 63 80 100 125M8V3...
Page 232: ...SiENBE34 703 Option List Appendix 221...
Page 235: ...Example of Connection SiENBE34 703 224 Appendix...
Page 241: ...Method of Replacing the Inverter s Power Transistors Modules SiBE34 703 230 Appendix...
Page 261: ...RXYSQ4 5 6 P7Y1B SiENBE34 703 250 Removal Procedure...