SiENBE34-703
Troubleshooting by Indication on the Centralized remote control
Troubleshooting
181
4. Troubleshooting by Indication on the Centralized
remote control
4.1
“
UE
”
Malfunction of Transmission between Centralized
remote control and Indoor Unit
remote control
Display
UE
Applicable
Models
AII indoor unit models
Centralized remote control
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor unit and central remote control is normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
!
Malfunction of transmission between optional controllers for centralized control and indoor unit
!
Connector for setting master controller is disconnected.
!
Failure of PC board for central remote control
!
Defect of indoor unit PC board
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Caution
Is the power supply
turned on for indoor
units displaying
malfunction?
Is transmission
wiring disconnected
or wired incorrectly?
Is the transmission wiring
with the master controller
disconnected or wired
incorrectly?
Is the master
controller's connector
for setting master
controller
disconnected?
Set the group No. correctly.
Replace indoor unit PC board.
Fix the wiring correctly.
Fix the wiring correctly.
Connect the connector
correctly.
Replace the central PC board.
Reset power supply
simultaneously for all optional
controllers for centralized
control.
Turn indoor unit's power
supply.
Has an indoor unit
once connected been
remove or its address
changed?
Is the group No. of
malfunctioning indoor
units set?
Is transmission with
all indoor units
malfunctioning?
(V2832)
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
Summary of Contents for VRVIII-S
Page 1: ...SiENBE34 703 Basic Training Manual R 410A Heat Pump 50Hz Service Manual...
Page 11: ...Introduction SiENBE34 703 x...
Page 113: ...Field Setting SiENBE34 703 102 Test Operation...
Page 207: ...Troubleshooting by Indication on the Unified ON OFF Control SiENBE34 703 196 Troubleshooting...
Page 215: ...Wiring Diagrams SiENBE34 703 204 Appendix 2 3 Indoor Unit FXCQ20 25 32 63M8...
Page 216: ...SiENBE34 703 Wiring Diagrams Appendix 205 FXCQ40 50 80 125M8V3...
Page 217: ...Wiring Diagrams SiENBE34 703 206 Appendix FXFQ25 32 40 50 63 80 100 125P7VE...
Page 218: ...SiENBE34 703 Wiring Diagrams Appendix 207 FXZQ20 25 32 40 50M8V1...
Page 221: ...Wiring Diagrams SiENBE34 703 210 Appendix FXDQ20 25M8V3...
Page 222: ...SiENBE34 703 Wiring Diagrams Appendix 211 FXSQ20 25 32 40 50 63 80 100 125M8V3...
Page 232: ...SiENBE34 703 Option List Appendix 221...
Page 235: ...Example of Connection SiENBE34 703 224 Appendix...
Page 241: ...Method of Replacing the Inverter s Power Transistors Modules SiBE34 703 230 Appendix...
Page 261: ...RXYSQ4 5 6 P7Y1B SiENBE34 703 250 Removal Procedure...