Troubleshooting by Indication on the remote control
SiENBE34-703
140
Troubleshooting
Troubleshooting
+5V
(4)
(3)
(2)
(1)
Check for the points shown below.
1
Is the stop valve open?
2
Is the HPS connector properly connected to the
main PCB?
3
Does the high pressure switch have continuity?
Are the three points
above OK?
Rectify defective points, if any.
· Mount a pressure gauge on the high-pressure service port.
· Connect the Service Checker.
· Reset the operation using the remote control,
and then restart the operation.
Does the stop due to
malfunction (E3)
recur?
Is the HPS
operating value
normal (i.e.,
4.0MPa)?
Replace the HPS.
Replace the high pressure sensor.
Replace the main PCB.
· The high pressure sensor is normal, and the pressure detected with the PCB is also normal.
· The high pressure has really become high.
CHECK 1
Refer to information on P.193, remove the causes by which
the high pressure has become high.
*1: Make a comparison between the voltage of the pressure sensor (*4) and that read by the
pressure gauge.
(As to the voltage of the pressure sensor, make measurement of voltage at the connector,
and then convert it to pressure according to information on P.225.)
*2: Make a comparison between the high pressure value checked with the Service Checker
and the voltage of the pressure sensor (see *1).
*3: Make measurement of voltage of the pressure sensor.
Make measurement of DC voltage between these wires. (*4)
Are the
characteristics of the
high pressure sensor
normal?
(See *1.)
Is the pressure
detected with the PCB
normal? (See *2.)
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
High
pressure
sensor
Red
Black
White
Connector for high
pressure sensor (Red)
Micro controller
A/D input
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Caution
Summary of Contents for VRVIII-S
Page 1: ...SiENBE34 703 Basic Training Manual R 410A Heat Pump 50Hz Service Manual...
Page 11: ...Introduction SiENBE34 703 x...
Page 113: ...Field Setting SiENBE34 703 102 Test Operation...
Page 207: ...Troubleshooting by Indication on the Unified ON OFF Control SiENBE34 703 196 Troubleshooting...
Page 215: ...Wiring Diagrams SiENBE34 703 204 Appendix 2 3 Indoor Unit FXCQ20 25 32 63M8...
Page 216: ...SiENBE34 703 Wiring Diagrams Appendix 205 FXCQ40 50 80 125M8V3...
Page 217: ...Wiring Diagrams SiENBE34 703 206 Appendix FXFQ25 32 40 50 63 80 100 125P7VE...
Page 218: ...SiENBE34 703 Wiring Diagrams Appendix 207 FXZQ20 25 32 40 50M8V1...
Page 221: ...Wiring Diagrams SiENBE34 703 210 Appendix FXDQ20 25M8V3...
Page 222: ...SiENBE34 703 Wiring Diagrams Appendix 211 FXSQ20 25 32 40 50 63 80 100 125M8V3...
Page 232: ...SiENBE34 703 Option List Appendix 221...
Page 235: ...Example of Connection SiENBE34 703 224 Appendix...
Page 241: ...Method of Replacing the Inverter s Power Transistors Modules SiBE34 703 230 Appendix...
Page 261: ...RXYSQ4 5 6 P7Y1B SiENBE34 703 250 Removal Procedure...