Troubleshooting by Remote Control
SiENBE34-703
116
Troubleshooting
8
: ON
7
: OFF
9
: Blink
Malfunction
code
Operation
lamp
Inspection
display
Unit No.
Malfunction contents
Page
Referred
Indoor Unit
A0
9
9
9
Error of external protection device
122
A1
9
9
9
PC board defect, E
2
PROM defect
123
A3
9
9
9
Malfunction of drain level control system (S1L)
124
A6
9
9
9
Fan motor (M1F) lock, overload
126
A7
8
9
9
Malfunction of swing flap motor (M1S)
127
A9
9
9
9
Malfunction of moving part of electronic expansion
valve (Y1E)
129
AF
8
7
9
Drain level above limit
131
AJ
9
9
9
Malfunction of capacity setting
132
C4
9
9
9
Malfunction of thermistor (R2T) for heat exchange
(loose connection, disconnection, short circuit, failure)
133
C5
9
9
9
Malfunction of thermistor (R3T) for gas pipes (loose
connection, disconnection, short circuit, failure)
134
C9
9
9
9
Malfunction of thermistor (R1T) for air inlet (loose
connection, disconnection, short circuit, failure)
135
CA
9
9
9
Malfunction of thermistor for air inlet (loose
connection, disconnection, short circuit, failure)
136
CJ
8
9
8
Malfunction of thermostat sensor in remote control
137
Outdoor Unit
E1
9
9
9
PC board defect
138
E3
9
9
9
Actuation of high pressure switch
139
E4
9
9
9
Actuation of low pressure sensor
141
E5
9
9
9
Compressor motor lock
143
E6
9
9
9
Standard compressor lock or over current
—
E7
9
9
9
Malfunction of outdoor unit fan motor
144
E9
9
9
9
Malfunction of moving part of electronic expansion
valve (Y1E, Y2E)
145
F3
9
9
9
Abnormal discharge pipe temperature
147
F6
9
9
9
Refrigerant overcharged
148
H3
8
7
9
Failure of high pressure switch
—
H4
9
9
9
Actuation of low pressure switch
—
H7
9
9
9
Abnormal outdoor fan motor signal
—
H9
9
9
9
Malfunction of thermistor (R1T) for outdoor air (loose
connection, disconnection, short circuit, failure)
149
J2
9
9
9
Current sensor malfunction
—
J3
9
9
9
Malfunction of discharge pipe thermistor (R2T) (loose
connection, disconnection, short circuit, failure)
150
J5
9
9
9
Malfunction of thermistor (R3T, R5T) for suction pipe
(loose connection, disconnection, short circuit,
failure)
151
J6
9
9
9
Malfunction of thermistor (R6T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
152
J7
9
9
9
Malfunction of receiver outlet liquid pipe thermistor (R7T)
153
J9
9
9
9
Malfunction of subcooling heat exchanger gas pipe
thermistor (R4T)
154
JA
9
9
9
Malfunction of discharge pipe pressure sensor
155
JC
9
9
9
Malfunction of suction pipe pressure sensor
156
L0
9
9
9
Inverter system error
—
L1
9
9
9
Malfunction of PC board
157
L4
9
9
9
Malfunction of inverter radiating fin temperature rise
158
L5
9
9
9
DC output overcurrent of inverter compressor
159
L8
9
9
9
Inverter current abnormal
160
L9
9
9
9
Inverter start up error
161
Summary of Contents for VRVIII-S
Page 1: ...SiENBE34 703 Basic Training Manual R 410A Heat Pump 50Hz Service Manual...
Page 11: ...Introduction SiENBE34 703 x...
Page 113: ...Field Setting SiENBE34 703 102 Test Operation...
Page 207: ...Troubleshooting by Indication on the Unified ON OFF Control SiENBE34 703 196 Troubleshooting...
Page 215: ...Wiring Diagrams SiENBE34 703 204 Appendix 2 3 Indoor Unit FXCQ20 25 32 63M8...
Page 216: ...SiENBE34 703 Wiring Diagrams Appendix 205 FXCQ40 50 80 125M8V3...
Page 217: ...Wiring Diagrams SiENBE34 703 206 Appendix FXFQ25 32 40 50 63 80 100 125P7VE...
Page 218: ...SiENBE34 703 Wiring Diagrams Appendix 207 FXZQ20 25 32 40 50M8V1...
Page 221: ...Wiring Diagrams SiENBE34 703 210 Appendix FXDQ20 25M8V3...
Page 222: ...SiENBE34 703 Wiring Diagrams Appendix 211 FXSQ20 25 32 40 50 63 80 100 125M8V3...
Page 232: ...SiENBE34 703 Option List Appendix 221...
Page 235: ...Example of Connection SiENBE34 703 224 Appendix...
Page 241: ...Method of Replacing the Inverter s Power Transistors Modules SiBE34 703 230 Appendix...
Page 261: ...RXYSQ4 5 6 P7Y1B SiENBE34 703 250 Removal Procedure...