SiENBE34-703
Troubleshooting by Remote Control
Troubleshooting
117
Outdoor Unit
LA
9
9
9
Malfunction of power unit
—
LC
9
9
9
Malfunction of transmission between inverter and
control PC board
162
P1
9
9
9
High voltage of capacitor in main inverter circuit.
163
System
U0
8
7
9
Low pressure drop due to refrigerant shortage or
electronic expansion valve failure
164
U1
9
9
9
Reverse phase / open phase
—
U2
9
9
9
Power supply insufficient or instantaneous failure
166
U3
9
9
9
Check operation is not completed.
168
U4
9
9
9
Malfunction of transmission between indoor and
outdoor units
169
U5
9
9
9
Malfunction of transmission between remote control
and indoor unit
171
U5
7
8
7
Failure of remote control PC board or setting during
control by remote control
171
U7
9
9
9
Malfunction of transmission between outdoor units
—
U8
9
9
7
Malfunction of transmission between main and sub
remote controls (malfunction of sub remote control)
172
U9
9
9
9
Malfunction of transmission between indoor unit and
outdoor unit in the same system
173
UA
9
9
9
Improper combination of indoor and outdoor units,
indoor units and remote control
175
UC
8
8
8
Address duplication of central remote control
176
UE
9
9
9
Malfunction of transmission between central remote
control and indoor unit
177
UF
9
9
9
Refrigerant system not set, incompatible wiring /
piping
179
UH
9
9
9
Malfunction of system, refrigerant system address
undefined
180
Central
remote
control and
Schedule
Timer
UE
9
9
9
Malfunction of transmission between central remote
control and indoor unit
181
M1
8
or
7
9
9
Central remote control PC board defect
Schedule timer PC board defect
182
M8
8
or
7
9
9
Malfunction of transmission between optional
controllers for centralized control
183
MA
8
or
7
9
9
Improper combination of optional controllers for
centralized control
184
MC
8
or
7
9
9
Address duplication, improper setting
186
Heat
Reclaim
Ventilation
64
8
7
9
Indoor unit’s air thermistor error
—
65
8
7
9
Outside air thermistor error
—
68
8
7
9
Malfunction of HVU
—
6A
8
7
9
Damper system alarm
—
6A
9
9
9
Damper thermistor error
—
6F
8
7
9
Malfunction of simple remote control
—
94
9
9
9
Internal transmission error
—
8
: ON
7
: OFF
9
: Blink
Malfunction
code
Operation
lamp
Inspection
display
Unit No.
Malfunction contents
Page
Referred
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
Summary of Contents for VRVIII-S
Page 1: ...SiENBE34 703 Basic Training Manual R 410A Heat Pump 50Hz Service Manual...
Page 11: ...Introduction SiENBE34 703 x...
Page 113: ...Field Setting SiENBE34 703 102 Test Operation...
Page 207: ...Troubleshooting by Indication on the Unified ON OFF Control SiENBE34 703 196 Troubleshooting...
Page 215: ...Wiring Diagrams SiENBE34 703 204 Appendix 2 3 Indoor Unit FXCQ20 25 32 63M8...
Page 216: ...SiENBE34 703 Wiring Diagrams Appendix 205 FXCQ40 50 80 125M8V3...
Page 217: ...Wiring Diagrams SiENBE34 703 206 Appendix FXFQ25 32 40 50 63 80 100 125P7VE...
Page 218: ...SiENBE34 703 Wiring Diagrams Appendix 207 FXZQ20 25 32 40 50M8V1...
Page 221: ...Wiring Diagrams SiENBE34 703 210 Appendix FXDQ20 25M8V3...
Page 222: ...SiENBE34 703 Wiring Diagrams Appendix 211 FXSQ20 25 32 40 50 63 80 100 125M8V3...
Page 232: ...SiENBE34 703 Option List Appendix 221...
Page 235: ...Example of Connection SiENBE34 703 224 Appendix...
Page 241: ...Method of Replacing the Inverter s Power Transistors Modules SiBE34 703 230 Appendix...
Page 261: ...RXYSQ4 5 6 P7Y1B SiENBE34 703 250 Removal Procedure...