3.2.2 Cool / Heat Mode Switching
There are the following 4 cool/heat switching modes.
$
Set cool/heat separately for each outdoor unit system by indoor unit remote control.
%
Set cool/heat separately for each outdoor unit system by cool/heat switching remote control.
&
Set cool/heat for more than one outdoor unit system simultaneously in accordance with
unified master outdoor unit by indoor unit remote control.
'
Set cool/heat for more than one outdoor unit system simultaneously in accordance with
unified master outdoor unit by cool/heat switching remote control.
$
Set Cool / Heat Separately for Each Outdoor Unit System by Indoor Unit remote control
#
It does not matter whether or not there is outdoor - outdoor unit wiring.
#
Set outdoor unit PC board DS1-1 to IN (factory set).
#
Set cool/heat switching to IND (individual) for “Setting mode 1” (factory set).
ON
OFF
MODE
DEMAND
L.N.O.P.
MASTER
IND
SLAVE
C/H SELECT R.C.
C/H SELECT
Dip SW
DS1-1
TEST
MALFUNC.
Indoor unit
Indoor unit
P1 P2
Remote
control
P1 P2
Remote
control
<Set the master unit (= indoor unit having the right to
select the cooling/heating operation mode).>
In the case of wired remote controls
• After the check operation,
“CHANGEOVER UNDER
CONTROL”
is flashing in all connected remote controls.
• Select an indoor unit to be used as the master unit in
accordance with the request from the customer.
(It is recommended to select an indoor unit which will be
used most often as the master unit.)
• Press the operation mode selector button in the remote
control of the indoor unit selected as the master unit.
• In that remote control,
“CHANGEOVER UNDER
CONTROL”
disappears. That remote control will control
changeover of the cooling/heating operation mode.
• In other remote controls,
“CHANGEOVER UNDER
CONTROL”
lights.
For the details, refer to the installation manual
supplied together with the indoor unit.
In the case of infrared remote controls
• After the check operation, the timer lamp is flashing in all
connected indoor units.
• Select an indoor unit to be used as the master unit in
accordance with the request from the customer.
(It is recommended to select an indoor unit which will be
used most often as the master unit.)
• Press the operation selector mode button in the remote
control of the indoor unit selected as the master unit. A
“peep” sound is emitted, and the timer lamp turns off in all
indoor units.
• That indoor unit will control changeover of the cooling/
heating operation mode.
Summary of Contents for VRVIII-S
Page 1: ...SiENBE34 703 Basic Training Manual R 410A Heat Pump 50Hz Service Manual...
Page 11: ...Introduction SiENBE34 703 x...
Page 113: ...Field Setting SiENBE34 703 102 Test Operation...
Page 207: ...Troubleshooting by Indication on the Unified ON OFF Control SiENBE34 703 196 Troubleshooting...
Page 215: ...Wiring Diagrams SiENBE34 703 204 Appendix 2 3 Indoor Unit FXCQ20 25 32 63M8...
Page 216: ...SiENBE34 703 Wiring Diagrams Appendix 205 FXCQ40 50 80 125M8V3...
Page 217: ...Wiring Diagrams SiENBE34 703 206 Appendix FXFQ25 32 40 50 63 80 100 125P7VE...
Page 218: ...SiENBE34 703 Wiring Diagrams Appendix 207 FXZQ20 25 32 40 50M8V1...
Page 221: ...Wiring Diagrams SiENBE34 703 210 Appendix FXDQ20 25M8V3...
Page 222: ...SiENBE34 703 Wiring Diagrams Appendix 211 FXSQ20 25 32 40 50 63 80 100 125M8V3...
Page 232: ...SiENBE34 703 Option List Appendix 221...
Page 235: ...Example of Connection SiENBE34 703 224 Appendix...
Page 241: ...Method of Replacing the Inverter s Power Transistors Modules SiBE34 703 230 Appendix...
Page 261: ...RXYSQ4 5 6 P7Y1B SiENBE34 703 250 Removal Procedure...