Special Control
SiENBE34-703
50
Function
3.5 Restart Standby
Restart is stood by force to prevent frequent power-on/off and to equalize pressure in the
refrigerant system.
Actuator
Operation
Remarks
Compressor
OFF
⎯
Outdoor unit fan
Ta>30
°
C: STEP4
Ta
≤
30
°
C: OFF
⎯
Four way valve
Keep former condition.
⎯
Main electronic expansion valve (EV1)
0 pls
⎯
Subcooling electronic expansion valve
(EV3)
0 pls
⎯
Hot gas bypass valve (SVP)
OFF
⎯
Ending conditions
2 min.
⎯