Troubleshooting by Indication on the remote control
SiENBE34-703
144
Troubleshooting
3.18
“
E7
”
Malfunction of Outdoor Unit Fan Motor
remote control
Display
E7
Applicable
Models
RXYSQ4~6P
Method of
Malfunction
Detection
Malfunction of fan motor system is detected according to the fan speed detected by hall IC
when the fan motor runs.
Malfunction
Decision
Conditions
!
When the fan runs with speed less than a specified one for 6 seconds or more when the fan
motor running conditions are met
!
When malfunction is generated 4 times, the system shuts down.
Supposed
Causes
!
Malfunction of fan motor
!
The harness connector between fan motor and PC board is left in disconnected, or faulty
connector
!
Fan does not run due to foreign matters tangled
!
Clearing condition: Operate for 5 minutes (normal)
!
Open phase L1 or open phase N.
Troubleshooting
Connect the connector.
Remove the obstacle.
Correct the power supply
voltage.
If L1 and N phases are
open, replace the switch
box.
Replace outdoor unit PC
board.
If the F4U has blown out,
replace the fuse.
If the F1U has blown out,
replace the inverter PC
board assy.
Replace the fan motor.
Are the
resistances between pins
above judgment?
Check No. 3
Check on connector of fan
motor (Refer to information
on P.195)
If the F4U has blown out,
replace the fuse.
If the F1U has blown out,
replace the inverter PC
board assy.
Replace the fan motor.
NO
YES
YES
YES
Connector of fan motor
is disconnected.
Can the fan be turned
smoothly with hand after
disconnect the connector
of fan motor?
Is there any
obstacle around
the fan?
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Has either the fuse F4U on
the control PC board (A1P)
or the fuse F1U on the
inverter PC board (A2P)
blown out?
Has the
voltage between L1
and N on the power supply
terminal board X1M fallen within the
range of 220 to 240V±10%
(50 Hz)?
Has either the fuse F4U
on the control PC board
(A1P) or the fuse F1U on
the inverter PC board
(A2P) blown out?
Caution
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
Summary of Contents for VRVIII-S
Page 1: ...SiENBE34 703 Basic Training Manual R 410A Heat Pump 50Hz Service Manual...
Page 11: ...Introduction SiENBE34 703 x...
Page 113: ...Field Setting SiENBE34 703 102 Test Operation...
Page 207: ...Troubleshooting by Indication on the Unified ON OFF Control SiENBE34 703 196 Troubleshooting...
Page 215: ...Wiring Diagrams SiENBE34 703 204 Appendix 2 3 Indoor Unit FXCQ20 25 32 63M8...
Page 216: ...SiENBE34 703 Wiring Diagrams Appendix 205 FXCQ40 50 80 125M8V3...
Page 217: ...Wiring Diagrams SiENBE34 703 206 Appendix FXFQ25 32 40 50 63 80 100 125P7VE...
Page 218: ...SiENBE34 703 Wiring Diagrams Appendix 207 FXZQ20 25 32 40 50M8V1...
Page 221: ...Wiring Diagrams SiENBE34 703 210 Appendix FXDQ20 25M8V3...
Page 222: ...SiENBE34 703 Wiring Diagrams Appendix 211 FXSQ20 25 32 40 50 63 80 100 125M8V3...
Page 232: ...SiENBE34 703 Option List Appendix 221...
Page 235: ...Example of Connection SiENBE34 703 224 Appendix...
Page 241: ...Method of Replacing the Inverter s Power Transistors Modules SiBE34 703 230 Appendix...
Page 261: ...RXYSQ4 5 6 P7Y1B SiENBE34 703 250 Removal Procedure...