Precautions for New Refrigerant (R-410A)
SiENBE34-703
236
Precautions for New Refrigerant (R-410A)
1. Flaring tool
!
Specifications
2
Dimension A
!
Differences
2
Change of dimension A
Conventional flaring tools can be used when the work process is changed.
(change of work process)
Previously, a pipe extension margin of 0 to 0.5mm was provided for flaring. For R-410A air
conditioners, perform pipe flaring with a pipe extension margin of 1.0 to 1.5mm.
(For clutch type only)
Conventional tool with pipe extension margin adjustment can be used.
Flare gauge
Nominal size
1/4
3/8
1/2
5/8
3/4
Tube O.D.
Do
6.35
9.52
12.70
15.88
19.05
Class-2 (R-410A)
9.1
13.2
16.6
19.7
24.0
Class-1 (Conventional)
9.0
13.0
16.2
19.4
23.3
+0
-0.4
A
Unit:mm
For class-1: R-407C
For class-2: R-410A
Dimension A
Summary of Contents for VRVIII-S
Page 1: ...SiENBE34 703 Basic Training Manual R 410A Heat Pump 50Hz Service Manual...
Page 11: ...Introduction SiENBE34 703 x...
Page 113: ...Field Setting SiENBE34 703 102 Test Operation...
Page 207: ...Troubleshooting by Indication on the Unified ON OFF Control SiENBE34 703 196 Troubleshooting...
Page 215: ...Wiring Diagrams SiENBE34 703 204 Appendix 2 3 Indoor Unit FXCQ20 25 32 63M8...
Page 216: ...SiENBE34 703 Wiring Diagrams Appendix 205 FXCQ40 50 80 125M8V3...
Page 217: ...Wiring Diagrams SiENBE34 703 206 Appendix FXFQ25 32 40 50 63 80 100 125P7VE...
Page 218: ...SiENBE34 703 Wiring Diagrams Appendix 207 FXZQ20 25 32 40 50M8V1...
Page 221: ...Wiring Diagrams SiENBE34 703 210 Appendix FXDQ20 25M8V3...
Page 222: ...SiENBE34 703 Wiring Diagrams Appendix 211 FXSQ20 25 32 40 50 63 80 100 125M8V3...
Page 232: ...SiENBE34 703 Option List Appendix 221...
Page 235: ...Example of Connection SiENBE34 703 224 Appendix...
Page 241: ...Method of Replacing the Inverter s Power Transistors Modules SiBE34 703 230 Appendix...
Page 261: ...RXYSQ4 5 6 P7Y1B SiENBE34 703 250 Removal Procedure...