Troubleshooting by Indication on the remote control
SiENBE34-703
170
Troubleshooting
Troubleshooting
∗
: Refer to information on P.195.
(V3187)
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Caution
Repair the broken wires, and
then restart operation.
Replace the fuse.
Fix the indoor/outdoor unit
transmission wiring.
Push and hold the RESET
button on the outdoor unit PC
board for 5 seconds.
Replace the outdoor unit PC
board (A1P).
Replace the indoor unit PC
board.
Push and hold the RESET
button on the master outdoor
unit PC Board for 5 seconds.
Fix the indoor/outdoor unit
transmission wiring.
Has the
indoor or
outdoor unit PC
board been replaced, or
has the indoor - outdoor or
outdoor - outdoor unit
transmission wiring
been modified?
All
indoor
unit remote
controls of the same
refrigerant system
display"U4."
Outdoor unit PC
boardmicrocomputer
monitor(HAP) blinks.
Operation ready
lamp (H2P) is
blinking.
Lamp does not go
off for 12 minutes or
more.
The fuse F3U on the
outdoor unit's PC board
is burnt.
Check No. 3
∗
Check for the fan motor
connector.
Replace outdoor unit PC
board (A1P).
Has either
the fuse F4U on the
outdoor unit PC board (A1P)
or the fuse F1U on the inverter PC
board (A2P) blown out?
Are
there any broken
wires in the connectors of the
inverter PC board (A1P) and the control PC
board (A2P)?
Reset the power supply.
Supply 220~240 V.
Replace the fuse F4U and
the inverter PC board (A2P).
Replace the fan motor.
Replace the inverter PC
board.
Replace the fuse F4U.
∗
The unit will not operate
forup to 12 minutes.
YES
YES
NO
NO
NO
NO
NO
NO
YES
YES
YES
Is indoor -
outdoor and outdoor
- outdoor unit transmission
wiring normal?
The voltage between
terminals L3 and N of the
outdoor unit PC board is
220~240 V.
YES
YES
NO
YES
Is resistance
between pins in
excess of judgment
criteria?
Is
indoor -
outdoor and outdoor -
outdoor unit transmission
wiring normal?
YES
NO
NO
YES
YES
NO
NO
YES
Check No.3
Summary of Contents for VRVIII-S
Page 1: ...SiENBE34 703 Basic Training Manual R 410A Heat Pump 50Hz Service Manual...
Page 11: ...Introduction SiENBE34 703 x...
Page 113: ...Field Setting SiENBE34 703 102 Test Operation...
Page 207: ...Troubleshooting by Indication on the Unified ON OFF Control SiENBE34 703 196 Troubleshooting...
Page 215: ...Wiring Diagrams SiENBE34 703 204 Appendix 2 3 Indoor Unit FXCQ20 25 32 63M8...
Page 216: ...SiENBE34 703 Wiring Diagrams Appendix 205 FXCQ40 50 80 125M8V3...
Page 217: ...Wiring Diagrams SiENBE34 703 206 Appendix FXFQ25 32 40 50 63 80 100 125P7VE...
Page 218: ...SiENBE34 703 Wiring Diagrams Appendix 207 FXZQ20 25 32 40 50M8V1...
Page 221: ...Wiring Diagrams SiENBE34 703 210 Appendix FXDQ20 25M8V3...
Page 222: ...SiENBE34 703 Wiring Diagrams Appendix 211 FXSQ20 25 32 40 50 63 80 100 125M8V3...
Page 232: ...SiENBE34 703 Option List Appendix 221...
Page 235: ...Example of Connection SiENBE34 703 224 Appendix...
Page 241: ...Method of Replacing the Inverter s Power Transistors Modules SiBE34 703 230 Appendix...
Page 261: ...RXYSQ4 5 6 P7Y1B SiENBE34 703 250 Removal Procedure...