Troubleshooting by Indication on the remote control
SiENBE34-703
154
Troubleshooting
3.27
“
J9
”
Outdoor Unit: Malfunction of Subcooling Heat
Exchanger Gas Pipe Thermistor (R4T)
remote control
Display
J9
Applicable
Models
RXYSQ4~6P
Method of
Malfunction
Detection
Malfunction is detected according to the temperature detected by subcooling heat exchanger
gas pipe thermistor.
Malfunction
Decision
Conditions
When the subcooling heat exchanger gas pipe thermistor is short circuited or open.
Supposed
Causes
!
Faulty subcooling heat exchanger gas pipe thermistor (R4T)
!
Faulty outdoor unit PC board
Troubleshooting
∗
Refer to “Thermistor Resistance / Temperature Characteristics” table on P225.
(V3075)
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Caution
Is
the
resistance
measured after
removing the thermistor (R4T)
from outdoor unit PC board
normal?
(3.5 k
Ω
to 360 k
Ω
)
Replace outdoor unit PC board
(A1P).
Connect connector and operate
unit again.
Replace thermistor (R4T).
Is
the
connector for
subcooling heat
exchanger gas pipe
thermistor connected to
X12A of outdoor unit
PC board
(A1P)?
NO
NO
YES
YES
Summary of Contents for VRVIII-S
Page 1: ...SiENBE34 703 Basic Training Manual R 410A Heat Pump 50Hz Service Manual...
Page 11: ...Introduction SiENBE34 703 x...
Page 113: ...Field Setting SiENBE34 703 102 Test Operation...
Page 207: ...Troubleshooting by Indication on the Unified ON OFF Control SiENBE34 703 196 Troubleshooting...
Page 215: ...Wiring Diagrams SiENBE34 703 204 Appendix 2 3 Indoor Unit FXCQ20 25 32 63M8...
Page 216: ...SiENBE34 703 Wiring Diagrams Appendix 205 FXCQ40 50 80 125M8V3...
Page 217: ...Wiring Diagrams SiENBE34 703 206 Appendix FXFQ25 32 40 50 63 80 100 125P7VE...
Page 218: ...SiENBE34 703 Wiring Diagrams Appendix 207 FXZQ20 25 32 40 50M8V1...
Page 221: ...Wiring Diagrams SiENBE34 703 210 Appendix FXDQ20 25M8V3...
Page 222: ...SiENBE34 703 Wiring Diagrams Appendix 211 FXSQ20 25 32 40 50 63 80 100 125M8V3...
Page 232: ...SiENBE34 703 Option List Appendix 221...
Page 235: ...Example of Connection SiENBE34 703 224 Appendix...
Page 241: ...Method of Replacing the Inverter s Power Transistors Modules SiBE34 703 230 Appendix...
Page 261: ...RXYSQ4 5 6 P7Y1B SiENBE34 703 250 Removal Procedure...