2.3
Electronic Expansion Valve PI Control R-410A
circuit
Main Electronic Expansion Valve EV1 Control - Outdoor Unit
Carries out the electronic expansion valve (Y1E) PI control to maintain the evaporator outlet
superheated degree (SH) at constant during heating operation to make maximum use of the
outdoor unit heat exchanger (evaporator).
The optimum initial value of the evaporator outlet superheated degree is 3°C, but varies
depending on the discharge pipe superheated degree of inverter compressor.
Subcooling Electronic Expansion Valve EV3 Control - Outdoor Unit
Makes PI control of the electronic expansion valve (Y3E) to keep the superheated degree
(SH)
of the outlet gas pipe on the evaporator side for the full use of the subcooling heat exchanger.
Electronic Expansion Valve K1E Control - Indoor Unit
Carries out the electronic expansion valve (K1E) PI control to maintain the condensor outlet
subcooled degree (SC) at constant during heating operation to make maximum use of the
indoor unit heat exchanger (condensor).
2.4
Electronic Expansion Valve PI Control R-134a
circuit
Electronic Expansion Valve K2E Control - Indoor Unit
Carries out the electronic expansion valve (K1E) PI control to maintain the condensor outlet
subcooled degree (SC) at constant during heating operation to make maximum use of the
indoor unit heat exchanger (condensor).
SH = Ts1 - Te
SH : Evaporator outlet superheated degree (°C)
Ts1 : Suction pipe temperature detected by
thermistor R3T (°C)
Te : Low pressure equivalent saturation temperature
(°C)
SH = Tsh
- Te
SH : Outlet superheated degree of evaporator (
°
C)
Tsh : Suction pipe temperature detected with the
thermistor R4T (
°
C)
Te : Low pressure equivalent saturation temperature
(
°
C)
SC = Tc - R3T
SC = Tc - R7T
Summary of Contents for ERSQ 011AAV1
Page 2: ......
Page 12: ...Introduction ESIE09 08 x...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08 4 General Information...
Page 22: ...Specifications ESIE09 08 10 Specifications...
Page 38: ...Functional Parts Layout ESIE09 08 26 Refrigerant Circuit...
Page 248: ...Method of Replacing the Inverter s Power Transistors Modules ESIE09 08 236 Appendix...