Troubleshooting by Indication on the Remote Controller
Troubleshooting
157
3.20
“E9”
Outdoor Unit: Malfunction of Moving Part of
Electronic Expansion Valve
Remote Control
Display
E9
Applicable
Models
ER*Q 011~016*
Method of
Malfunction
Detection
Check disconnection of connector
Check continuity of expansion valve coil
Malfunction
Decision
Conditions
Error is generated under no common power supply when the power is on.
Supposed
Causes
Defect of moving part of electronic expansion valve
Defect of outdoor unit PC board (A1P)
Defect of connecting cable
Troubleshooting
(V3067)
YES
Caution
Be sure to turn off power switch before connecting or disconnecting connector,
otherwise parts may be damaged.
Return to normal?
Turn power supply off, and
turn power supply on again.
Electronic
expansion valve is
connected to X21A and X22A
of outdoor unit PC
board (A1P)
The
connecting cable is
short-circuited or
disconnected.
Replace the connecting cable.
Replace outdoor unit PC board
(A1P).
NO
NO
NO
NO
Replace the moving part of the
electronic expansion valve.
External factor other than
malfunction (for example, noise
etc.).
After connecting, turn the power
off and then back on again.
YES
YES
YES
Summary of Contents for ERSQ 011AAV1
Page 2: ......
Page 12: ...Introduction ESIE09 08 x...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08 4 General Information...
Page 22: ...Specifications ESIE09 08 10 Specifications...
Page 38: ...Functional Parts Layout ESIE09 08 26 Refrigerant Circuit...
Page 248: ...Method of Replacing the Inverter s Power Transistors Modules ESIE09 08 236 Appendix...