ESIE09-08
Troubleshooting by Indication on the Remote Controller
Troubleshooting
131
3.2
“A6”
Indoor Unit: Pump Error (M1P) or Other Water
System Error
Remote Control
Display
A6
Subcode 0
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Detection by failure of signal for detecting number of turns to come from the pump motor.
Detection by failure ref. sensors.
Malfunction
Decision
Conditions
When number of turns cannot be detected even when output voltage to the pump motor is
maximum. When water sensors are not within expected range.
Supposed
Causes
Pump rotor locked
Disconnected or faulty wiring between pump connector and PC board (A1P)
Blocked waterflow or heat exchanger (waterside)
Troubleshooting
Caution
Be sure to turn off power switch before connecting or disconnecting connector,
otherwise parts may be damaged.
Connect the wiring and turn on again.
Fix the wiring and turn on again.
YES
NO
NO
NO
NO
NO
YES
YES
Replace the indoor unit PC board.
Replace the pump motor.
(V2779)
Is the
wiring from the
pump securely connected
to connectors (X20A) on the
indoor unit PC board?
(A1P)
Wiring
between the indoor
unit PC board and pump is
disconnected.
Does the pump run?
YES
Can be checked - Too high T° difference
|Return water
- R-134a liquid T°|>40°C
|Leaving water T° - condense temp|>15°C
- Too small T° difference
|Leaving water
- return water temp|<1°C
Is the
waterflow or heat
exchanger
blocked?
YES
Make sure all valves are open.
Make sure filter is not clogged.
Make that sure water pressure is OK
(0,3bar<P<3bar).
Make sure that all valves are open.
Make sure that all air is out of the system.
Is the pump
rotor locked?
Summary of Contents for ERSQ 011AAV1
Page 2: ......
Page 12: ...Introduction ESIE09 08 x...