ESIE09-08
Special Control
Function
55
3.4
Stopping Operation
Operation of the actuator when the system is down, is cleared up.
3.4.1 When System is in Stop Mode
OUTDOOR
INDOOR
Actuator
Operation
Compressor
OFF
Outdoor unit fan
OFF
Four way valve
Keep former condition.
Main electronic expansion valve (EV1)
0 pls
Subcooling electronic expansion valve (EV3)
0 pls
Hot gas bypass valve (SVP)
OFF
Ending conditions
Request for space heating OR hot water
production
Actuator
Operation
Compressor
OFF
4-way valve
Keep former condition.
Pump
OFF
Electronic expansion valve K1E - R-410A
0 pls
Electronic expansion valve K2E - R-134a
0 pls
Ending conditions
Request for space heating OR hot water
production