Troubleshooting by Indication on the Remote Controller
ESIE09-08
206
Troubleshooting
[CHECK 1] Check for causes of rise in high pressure
Referring to the Fault Tree Analysis (FTA) shown below, probe the faulty points.
Short circuit
Rise in high
pressure
Local
pressure
rise
High pipe
resistance
Stop valve closed
Bent or crashed pipe
Clogging of foreign
particles
←Check to be sure the stop valve is open.
←Conduct visual checks for pipe conditions.
←Is there any temperature difference caused before
and after the filter or branch pipe.
Faulty indoor
unit electronic
expansion valve
←Are the coil resistance and insulation
normal?
Faulty high
pressure
control
Faulty valve coil
Faulty valve body
[In heating]
If the indoor unit electronic
expansion valve excessively
throttled:
(See *1.)
Faulty
control
Faulty high pressure sensor
Faulty indoor unit
liquid pipe thermistor
Faulty control PCB
←Are the electrical characteristics normal?
←In the connector properly connected?
Are the thermistor resistance characteristics normal?
←Is the pressure value checked with the Service Checker
corresponding to the measurement of the pressure
sensor?
High suction
air
temperature
of the
condenser
[In heating]
High suction air
temperature of
indoor unit
High ambient temperature
←Is the suction air temperature not more than 27°C?
←Is the indoor temperature not more than 27°C?
Faulty suction air thermistor of indoor unit
High suction air temperature of outdoor unit
Faulty outdoor temperature thermistor of outdoor unit
←Is the connector properly connected?
Are the thermistor resistance characteristics normal?
←Is the outdoor temperature not more than 16°CWB?
←Is the connector properly connected?
Are the thermistor resistance characteristics normal?
Degradation
in condensing
capacity
Dirty condenser
Mixing of non-condensable gas
←Is the heat exchanger clogged? (In cooling)
←Is air or else mixed in the refrigerant system?
Decreased
fan airflow
rate
Decreased
fan
output
Faulty fan
motor
←Can the fan motor be rotated with hands?
Are the motor coil resistance and insulation
normal?
←If a spare PC board is mounted, is the
capacity setting properly made?
Faulty control
PC board
(Including
capacity setting)
High air
passage
resistance
Dirty filter
←Is the air filter clogged?
Obstacle
←Is there any obstacle in the air passage?
Excessive refrigerant charging
Improper model selection
[In heating]
←Refer to P.173.
←Is the indoor unit too small compared to
the large-sized outdoor unit?
*1: In heating, the indoor unit electronic expansion valve is used for “subcooled degree control”.
(For details, refer to “Electronic Expansion Valve Control” on P.72.)
C: SDK04009
Summary of Contents for ERSQ 011AAV1
Page 2: ......
Page 12: ...Introduction ESIE09 08 x...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08 4 General Information...
Page 22: ...Specifications ESIE09 08 10 Specifications...
Page 38: ...Functional Parts Layout ESIE09 08 26 Refrigerant Circuit...
Page 248: ...Method of Replacing the Inverter s Power Transistors Modules ESIE09 08 236 Appendix...