ESIE09-08
Troubleshooting by Indication on the Remote Controller
Troubleshooting
171
3.32
“JA”
Outdoor Unit: Malfunction of High Pressure Sensor
Remote Control
Display
JA
Applicable
Models
ER*Q 011~016*
Method of
Malfunction
Detection
Malfunction is detected from the pressure detected by the high pressure sensor.
Malfunction
Decision
Conditions
When the high pressure sensor is short circuit or open circuit.
Supposed
Causes
Defect of high pressure sensor
Connection of low pressure sensor with wrong connection
Defect of outdoor unit PC board
Troubleshooting
∗
1: Voltage measurement point
∗
2: Refer to “Pressure Sensor”, pressure / voltage characteristics table on P232.
(V2806)
Caution
Be sure to turn off power switch before connecting or disconnecting connector,
otherwise parts may be damaged.
The
relationship
between the *1
VH and high pressure is
normal (see *2) when voltage
is measured between
X17A pins (1) and (3) of
indoor unit PC board
(A1P) (see *1).
Replace the high pressure sensor.
Connect the high pressure sensor
and turn on again.
NO
NO
Replace indoor unit PC board
(A1P).
YES
YES
The high
pressure sensor is
connected to X17A of
indoor unit PC
board (A1P).
Indoor unit PC board A4P
+5V
X17A
Red
Black
White
GND
*2 Measure DC voltage here.
H
igh pr
essur
e sensor
4
3
2
1
(V2807)
Microcomputer
A/D input
Summary of Contents for ERSQ 011AAV1
Page 2: ......
Page 12: ...Introduction ESIE09 08 x...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08 4 General Information...
Page 22: ...Specifications ESIE09 08 10 Specifications...
Page 38: ...Functional Parts Layout ESIE09 08 26 Refrigerant Circuit...
Page 248: ...Method of Replacing the Inverter s Power Transistors Modules ESIE09 08 236 Appendix...