ESIE09-08
Troubleshooting by Indication on the Remote Controller
Troubleshooting
133
∗
1: Coil check method for the moving part of the electronic expansion valve
Discount the electronic expansion valve from the PC board and check the continuity between
the connector pins.
(Normal)
{
: Continuity
×: No continuity
Pin No.
1. White
2. Yellow
3. Orange
4. Blue
5. Red
6. Brown
1. White
×
{
Approx.
300
Ω
×
{
Approx.
150
Ω
×
2. Yellow
×
{
Approx.
300
Ω
×
{
Approx.
150
Ω
3. Orange
×
{
Approx.
150
Ω
×
4. Blue
×
{
Approx.
150
Ω
5. Red
×
6. Brown
Summary of Contents for ERSQ 011AAV1
Page 2: ......
Page 12: ...Introduction ESIE09 08 x...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08 4 General Information...
Page 22: ...Specifications ESIE09 08 10 Specifications...
Page 38: ...Functional Parts Layout ESIE09 08 26 Refrigerant Circuit...
Page 248: ...Method of Replacing the Inverter s Power Transistors Modules ESIE09 08 236 Appendix...