ESIE09-08
Field Setting
Test Operation
97
[9] Automatic temperature compensation
If needed, it is possible to adjust some thermistor value of the unit by a correction value. This
can be used as countermeasure for thermistor tolerances or capacity shortage.
The compensated temperature (= measured temperature plus compensation value) is then
used for controlling the system and will be displayed in the temperature read-out mode.
[9-00]
Leaving water temperature compensation value
[9-01]
Domestic hot water tank compensation value
[9-02]
Thermo ON/OFF admission
By changing this value the operation range for space heating operation can be modified.
If the ambient temperature becomes higher than (24°C + the value of [9-02]) no space
heating is possible.
Space heating can be requested as long as the ambient temperature is lower than (20°C +
the value of [9-02]).
Example:
[9-02] = –2°C
First
code
Second
code
Setting name
Default
value
Range
Step
Unit
9
Automatic temperature compensation
00
Leaving water temperature compensation
value
0
–5~5
0.5
°C
01
Domestic hot water tank compensation value
0
–5~5
0.5
°C
02
Thermo ON/OFF admission
0
–5~5
0.5
°C
A
No space heating operation possible
B
Request for space heating possible
C
Hysteresis area
T
Ambient temperature
T
20
°
C–2
°
C =
18
°
C
24
°
C–2
°
C =
22
°
C
A
B
C
C
Summary of Contents for ERSQ 011AAV1
Page 2: ......
Page 12: ...Introduction ESIE09 08 x...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08 4 General Information...
Page 22: ...Specifications ESIE09 08 10 Specifications...
Page 38: ...Functional Parts Layout ESIE09 08 26 Refrigerant Circuit...
Page 248: ...Method of Replacing the Inverter s Power Transistors Modules ESIE09 08 236 Appendix...