ESIE09-08
Troubleshooting by Indication on the Remote Controller
Troubleshooting
201
3.58
“U7”
Indoor Unit: Malfunction of Transmission Outdoor
Unit
Remote Control
Display
U7
Subcode 2
Applicable
Models
ER*Q 011~016*
Method of
Malfunction
Detection
Microcomputer checks the transmission of outdoor unit.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Improper connection of transmission wiring between outdoor unit and external control
adaptor for outdoor unit
Improper cool/heat selection
Improper cool/heat unified address (outdoor unit, external control adaptor for outdoor unit)
Defect of outdoor unit PC board (A1P)
Defect of external control adaptor for outdoor unit
Troubleshooting
Caution
Be sure to turn off power switch before connecting or disconnecting connector,
otherwise parts may be damaged.
(V2824)
C/H
SELECT is set to “IND”.
Replace the outdoor unit PC
Board (A1P).
YES
Cool/heat selection is
unified.
Set C/H SELECT to “IND”.
NO
NO
C/H SELECT is set to
“MASTER”.
C/H SELECT is set to
“SLAVE”.
Set C/H SELECT to “IND”.
YES
YES
Set C/H SELECT to “IND”.
Replace the outdoor unit PC
board (A1P).
NO
NO
YES
( )
( )
( )
( ) To select “IND”, press the BS2 button (set) till H3P led is on. Then press BS3 button (return) to confirm.
Summary of Contents for ERSQ 011AAV1
Page 2: ......
Page 12: ...Introduction ESIE09 08 x...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08 4 General Information...
Page 22: ...Specifications ESIE09 08 10 Specifications...
Page 38: ...Functional Parts Layout ESIE09 08 26 Refrigerant Circuit...
Page 248: ...Method of Replacing the Inverter s Power Transistors Modules ESIE09 08 236 Appendix...