Field Setting
ESIE09-08
90
Test Operation
[2] Automatic setback function
Setback function provides the possibility to lower the room temperature. The setback function
can for instance be activated during the night because the temperature demands during night
and day are not the same.
Notes :
1. By default the setback function is enabled, if it’s not needed, it should be disabled.
2. The setback function can be combined with the automatic weather dependent set point
operation.
3. Setback function is an automatic daily scheduled function.
4. It is advised to set the start time of automatic storage during night [1-01] on the moment that
the setback function starts [2-01].
[2-00]
Status: defines whether the setback function is turned ON (1) or OFF (0)
[2-01]
Start time: time at which setback is started
[2-02]
Stop time: time at which setback is stopped
* Setback operation for room temperature control
* Setback operation for leaving water control
Notes :
1. In setback operation for room temperature control, immediately a setback temperature is
set.
2. In setback operation for leaving water control, a shift down value is chosen. This value
should be lowered from the normal set point.
First
code
Second
code
Setting name
Default
value
Range
Step
Unit
2
Automatic setback function
00
Status: setback operation
1 (ON)
0/1
—
—
01
Setback operation start time
23:00
0:00~23:00
1:00
hour
02
Setback operation stop time
5:00
0:00~23:00
1:00
hour
A
Normal room temperature set point
t
Time
T
Temperature
[5-03]
Room setback temperature (actual temperature)
A
Normal leaving water temperature set point
B
Leaving water setback temperature
t
Time
T
Temperature
[5-02]
Leaving water setback value (shift value)
[2-01]
[2-02]
A
T
t
21
°
C
[5-03] 18
°
C
[2-01]
[2-02]
B
A
T
t
65
°
C
60
°
C
5
°
C [5-02]
Summary of Contents for ERSQ 011AAV1
Page 2: ......
Page 12: ...Introduction ESIE09 08 x...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08 4 General Information...
Page 22: ...Specifications ESIE09 08 10 Specifications...
Page 38: ...Functional Parts Layout ESIE09 08 26 Refrigerant Circuit...
Page 248: ...Method of Replacing the Inverter s Power Transistors Modules ESIE09 08 236 Appendix...