ESIE09-08
Basic Control
Function
49
2. Basic Control
2.1 Normal Operation
Heating Operation Outdoor Unit
+
Heating operation is not functional at an outdoor air temperature of field setting [9-02]. Default [20°C - 24°C].
Heating Operation Indoor Unit
Actuator
Operation
Remarks
Compressor
Compressor PI control
Used for high pressure protection control, low
pressure protection control, discharge pipe
temperature protection control, and compressor
operating frequency upper limit control with
inverter protection control.
Outdoor unit fan
STEP 7 or 8
All steps possible, mainly STEP 7 OR 8
Four way valve
ON
⎯
Main electronic expansion valve (EV1)
PI control
⎯
Subcooling electronic expansion valve
(EV3)
PI control
⎯
Hot gas bypass valve (SVP)
OFF
This valve turns on with low pressure protection
control.
Actuator
Operation
Remarks
Compressor
Compressor PI control
Used for high pressure protection control, low
pressure protection control, discharge pipe
temperature protection control, and compressor
operating frequency upper limit control with
inverter protection control.
Four way valve (Y1R)
OFF
Only activated during defrost.
Two way valve (K2S) = solenoid valve
CLOSED
Only open during defrost.
Electronic expansion valve (K1E)
PI control
⎯
Electronic expansion valve (K2E)
PI control
⎯
DC inverter pump
PI control
⎯
Summary of Contents for ERSQ 011AAV1
Page 2: ......
Page 12: ...Introduction ESIE09 08 x...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08 4 General Information...
Page 22: ...Specifications ESIE09 08 10 Specifications...
Page 38: ...Functional Parts Layout ESIE09 08 26 Refrigerant Circuit...
Page 248: ...Method of Replacing the Inverter s Power Transistors Modules ESIE09 08 236 Appendix...