ESIE09-08
Troubleshooting by Indication on the Remote Controller
Troubleshooting
199
3.56
“U4”
Malfunction of Transmission Indoor Unit
Remote Control
Display
U4
Subcode 4
Applicable
Models
AII indoor unit models
Method of
Malfunction
Detection
Microcomputer checks QA communication of indoor unit.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Wrong wiring between indoor unit PC boards. [A4P (1
ø
) or A5P (3
ø
)] and A1P
Troubleshooting
Caution
Replace indoor unit PC
board
Correct the wiring
YES
NO
Is the wiring
("1-2-3" communication
and upwiring)
normal?
Be sure to turn off power switch before connecting or disconnecting connector,
otherwise parts may be damaged.