Field Setting
ESIE09-08
102
Test Operation
[D] Domestic water heating retention times
The heat pump can only work in either space heating operation or domestic water heating
operation. No simultaneous operation is possible, except when using multiple set point control.
[d-00]
Set point: minimum operation time for domestic water heating
[d-01]
Set point: maximum operation time for domestic water heating
[d-02]
Set point: interval minimum stop time of domestic water heating
Changing the timer values can have an impact on space heating and domestic water heating
heat up timers. The default values are proposed but can be changed depending on the
complete system installation.
For a detailed explanation about simultaneous request of space heating and domestic water
heating, see control chapter.
First
code
Second
code
Setting name
Default
value
Range
Step
Unit
D
Domestic water heating retention times
00
Set point: minimum time for domestic water
heating
10
5~20
1
—
01
Set point: maximum time for domestic water
heating
30
10~60
5
—
02
Set point: interval minimum stop time of
domestic water heating
15
5~30
5
—