Basic Control
ESIE09-08
50
Function
2.2 Compressor PI Control
Compressor PI Control
Carries out the compressor capacity PI control to maintain Tc at constant during heating
operation to ensure stable unit performance.
Outdoor compressor (R-410A)
Indoor compressor (R-134a)
11kW -> max. 21 steps
14kW -> max. 26 steps
16kW -> max. 30 steps
STn
INV(Fullload) INV(Unload)
STn
INV(Fullload) INV(Unload)
STn
INV(Fullload) INV(Unload)
1
36.0Hz
11
80.0Hz
21
140.0Hz
2
39.0Hz
12
86.0Hz
22
146.0Hz
3
43.0Hz
13
92.0Hz
23
152.0Hz
4
47.0Hz
14
98.0Hz
24
158.0Hz
5
52.0Hz
15
104.0Hz
25
164.0Hz
6
52.0Hz
57.0Hz
16
110.0Hz
26
170.0Hz
7
57.0Hz
64.0Hz
17
116.0Hz
27
175.0Hz
8
62.0Hz
71.0Hz
18
122.0Hz
28
180.0Hz
9
68.0Hz
78.0Hz
19
128.0Hz
29
185.0Hz
10
74.0Hz
20
134.0Hz
30
190.0Hz
STEP
INV
STEP
INV
STEP
INV
1
40.0Hz
11
98.0Hz
21
158.0Hz
2
46.0Hz
12
104.0Hz
22
164.0Hz
3
52.0Hz
13
110.0Hz
23
170.0Hz
4
57.0Hz
14
116.0Hz
24
174.0Hz
5
62.0Hz
15
122.0Hz
25
182.0Hz
6
68.0Hz
16
128.0Hz
26
188.0Hz
7
74.0Hz
17
134.0Hz
27
194.0Hz
8
80.0Hz
18
138.0Hz
28
200.0Hz
9
86.0Hz
19
144.0Hz
29
206.0Hz
10
92.0Hz
20
152.0Hz
30
210.0Hz
∗
Compressors may operate in a pattern other than those listed in above tables subject to the operating conditions.
Selection of full load operation to/from unload operation is made with the unload circuit solenoid valve
(Y3S=SVUL). The full load operation is performed with the SVUL set to OFF, while the unload operation is
performed with the SVUL set to ON.
Summary of Contents for ERSQ 011AAV1
Page 2: ......
Page 12: ...Introduction ESIE09 08 x...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08 4 General Information...
Page 22: ...Specifications ESIE09 08 10 Specifications...
Page 38: ...Functional Parts Layout ESIE09 08 26 Refrigerant Circuit...
Page 248: ...Method of Replacing the Inverter s Power Transistors Modules ESIE09 08 236 Appendix...